Midea "Heat pumps monoblock commercial air-water RSJ series"

Operating ambient temperatures

Heating mode
- 15
... + 43 °C

Suggested retail price

188,600- ... 358,750-hrv.

    Heat pumps are constructed using the principle of heat transfer of ambient air energy to heat the water flowing through the heat exchanger, consumed in the farm or the engineering systems of buildings, through the reverse cycle of the operation of the refrigeration machine (heat pump).

    The assortment of this product consists of models of different heat output, and one device allows to provide water heating in volumes from 0.3 to 1 m³ of water per hour (with a maximum heating temperature of up to 60 ° C and an allowable range of outside air temperatures from -10 to +40 ° C At the same time, the coefficient of COP is the ratio of the amount of thermal energy produced to the consumed electric energy, in this series of products it reaches 4, which makes it possible to draw a conclusion about the high energy efficiency and tangible economic effect of such systems in The context of energy conservation policies and the use of "non-traditional" renewable sources of thermal energy.

    Commercial series of heat pumps designed for use in administrative and public buildings, as an alternative to gas or electric water heating systems for hot water.

    Strapping elements, vibration mounts, control panels (for 380 models) are not included in the delivery set. The units are designed to heat water in storage tanks.

    The units can be combined in a modular manner into a common circuit (for one storage tank) up to 16 units.

    Model name RSJ-200/SZN1-540V1
    Power supply V/Ph/Hz 380-415/3/50
    Water heating1 Capacity kW 20.4
    Rated power input kW 5.05
    COP 4.04
    Max. power input kW 7.80
    Max. input current A 13.3
    Compressor Type Scroll
    Quantity 1
    Capacity kW 16.2
    Input kW 5.2
    Rated current (RLA) A 9.1
    Locked rotor Amp (LRA) A 74
    Thermal protector ⁰C 135
    Refrigerant oil POE
    Outdoor fan Motor type AC motor
    Fan type Axial fan
    Number of fans 1
    Speed (H/L) r/min 900/580
    Air flow m3/h ≥5500
    Air side heat exchanger Type Finned tube
    Number of rows 2
    Number of circuits 10
    Water side heat exchanger Type Double-pipe heat exchanger
    Material Copper
    Refrigerant Type R410A
    Charged volume kg 2.9
    Throttle type Electronic expansion valve
    Outdoor noise level dB(A) 63
    Unit dimension (W×H×D) mm 790×1100×810
    Packing dimension (W×H×D) mm 860×1220×885
    Net/Gross weight kg 157/172
    Water piping connections Dia. Mm DN25
    Water pressure drop kPa 160
    Wire controller KJR-51/BMKE-A
    Hot water yield m3/h 0.45
    Ambient temperature range ⁰C -15 - 46
    Water outlet temperature range ⁰C 48-60    (default)55
    Notes:      
    1. The test conditions: outdoor temperature 20/15°C(DB/WB), inlet water temperature 15°C, outlet water temperature 55°C.
    Model name RSJ-420/SZN1-H
    Power supply V/Ph/Hz 380-415/3/50
    Water heating1 Capacity kW 39.0
    Rated power input kW 9.65
    COP 4.04
    Max. power input kW 14.5
    Max. input current A 24.0
    Compressor Type Scroll
    Quantity 1
    Capacity kW 29.2
    Input kW 9.2
    Rated current (RLA) A 20
    Locked rotor Amp
    (LRA)
    A 118
    Thermal protector ⁰C 135
    Refrigerant oil POE
    Outdoor fan Motor type AC motor
    Fan type Axial fan
    Number of fans 1
    Speed (H/L) r/min 850/750
    Air flow m3/h ≥12,000
    Air side heat exchanger Type Finned tube
    Number of rows 2
    Number of circuits 19
    Water side heat exchanger Type Double-pipe heat exchanger
    Material Copper
    Refrigerant Type R410A
    Charged volume kg 4.5
    Throttle type Electronic expansion valve
    Outdoor noise level dB(A) 66
    Unit dimension (W×H×D) mm 1,015×1,775×1,026
    Packing dimension (W×H×D) mm 1,070×1,900×1,030
    Net/Gross weight kg 323/343
    Water piping connections Dia. mm DN32
    Water pressure drop kPa 160
    Wire controller KJR-51/BMKE-A
    Hot water yield m3/h 0.89
    Ambient temperature range ⁰C -15 - 46
    Water outlet temperature range ⁰C 48-60    (default)56
    Notes:      
    1. The test conditions: outdoor temperature 20/15°C(DB/WB), inlet water temperature 15°C, outlet water temperature 55°C.