Midea "Outdoor modular unit VRF V6R series (Heat Recovery) DC-inverter"

Suggested retail price

373,100- ... 566,825-hrv.

    Sine-Wave Inverter

    Technology 180° -gradusnogo wave inverter conversion - control voltage without the "pulse" effects (jagged sinusoid).

    Compared with the current standard of 120° rectangular wave has the following advantages:

    1. Ability to work with a wider range of supply voltage and frequency.
    2. Most of the energy efficiency and energy conservation.
    3. More soft start, lower noise and vibration.
    4. more control.

    Outdoor unit design "Brilliant"

    Designers Midea did not forget about the exterior of the exterior unit of the air conditioner, which in itself is a rarity for climate technology. The outdoor unit is much more elegant than its counterparts, it has facets like a diamond, and attention to detail speaks of a high level of production and a carefully thought-out design concept.

    Multi-Bend Heat Exchanger

    Increased heat. This unit uses the heat exchangers with tubes of a special design, the inner surface of which has trapezoidal notches "Innergrove cooper", which provides maximum heat transfer surface area increased. Due to this heat increases by 28%, reduced power consumption, and hence increases the efficiency of the system.

    • 6 basic outdoor units, it is allowed to combine in 2- and 3-module assemblies (up to 168 kW).
    • The use of outdoor units of the VRF V6 HR series allows organizing the simultaneous operation of indoor units for heating and cold
    • The range of outdoor temperatures:

    - for cooling: –15 ° C ~ + 52 ° C;

    - for heating: –25 ° C ~ + 19 ° C;

    - for DHW preparation: –20 ° C ~ + 43 ° C.

    • In this series, it is possible to use hydronic modules with a power of 14 kW, which use part of the excess heat to heat hot water.
    • To connect indoor units, recuperation units are used. These units switch the refrigerant supplied and returned from each indoor unit, taking into account the selected operating mode and temperature parameters. In the MS recuperation units, the freon flows are redistributed, which allows the indoor units to operate in different modes at the same time.
    • The connection of indoor units to MS units is two-pipe, and the connection of MS units to the general line of the system (to the outdoor block) - three-pipe.
    • It is important to use such systems when there is an excess of heat (cold) in some of the serviced premises, while in others there is a shortage (for example, premises oriented in different cardinal points, data centers).
    HP 8 10 12
    Model name MV6-R252WV2GN1 MV6-R280WV2GN1 MV6-R335WV2GN1
    Power supply V/N/Hz 380-415/3/50(60)
    Cooling1 Capacity kW 22.4 28 33.5
    Power input kW 5.25 7.18 8.64
    EER 4.27 3.90 3.88
    Heating2(Rated) Capacity kW 22.4 28 33.5
    Power input kW 3.96 5.46 6.57
    COP 5.66 5.13 5.10
    Heating2(Max) Capacity kW 25 31.5 37.5
    Power input kW 4.69 7.12 9.48
    COP 5.33 4.43 3.95
    Connected indoor unit Total capacity 50-200% of outdoor unit capacity3
    Maximum quantity 64 64 64
    Compressor Type DC inverter
    Quantity 1
    Oil type FV68H
    Start-up method Soft start
    Fan Type Propeller
    Motor type DC
    Quantity 1
    Motor output kW 0.92 0.92 0.92
    Static pressure Pa 0,20,40,60,80(Selectable)
    Air flow rate m3/h 9000 9500 10000
    Drive type Direct
    Refrigerant Type R410A
    Factory charge kg 8 8 8
    Pipe connections4 Liquid pipe mm Φ12.7 Φ12.7 Φ12.7
    Low pressure gas pipe mm Φ25.4 Φ25.4 Φ25.4
    High pressure gas pipe mm Φ19.1 Φ19.1 Φ19.1
    Sound pressure level5 dB(A) 58 58 60
    Sound power level5 dB(A) 78 78 81
    Net dimensions (W×H×D) mm 990×1635×790 990×1635×790 990×1635×790
    Packed dimensions (W×H×D) mm 1090×1805×860 1090×1805×860 1090×1805×860
    Net weight kg 232 232 232
    Gross weight kg 248 248 248
    Ambient temp. operation range Cooling6 oC(DB) -15 ~ 52
    Heating oC(WB) -25 ~ 19
    Domestic hot water oC(DB) -20 ~ 43
    Notes:          
    1.     Indoor air temperature 27°C DB, 19°C WB; outdoor air temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
    2.     Indoor air temperature 20°C DB; outdoor air temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
    3.     Refer to table 1-5.1: Indoor and outdoor unit combination ratio limitations in Part 1.    
    4.     Diameters given are those of the unit's stop valve.        
    5.     Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.
    6.     -15°C to -5°C low temperature cooling operation is just available for MS01.    
    HP 14 16 18 20
    Model name MV6- R400WV2GN1 MV6- R450WV2GN1 MV6- R500WV2GN1 MV6- R560WV2GN1
    Power supply V/N/H 380-415/3/50(60)
    Cooling1 Capacity kW 40 45 50 56
    Power input kW 9.83 12.00 13.81 17.39
    EER 4.07 3.75 3.62 3.22
    Heating2(Rated) Capacity kW 40 45 50 56
    Power input kW 8.26 9.78 11.90 14.77
    COP 4.84 4.60 4.20 3.79
    Heating2(Max) Capacity kW 45 50 56 63
    Power input kW 9.78 12.26 14.77 18.33
    COP 4.60 4.08 3.79 3.44
    Connected
    indoor unit
    Total capacity 50-200% of outdoor unit capacity3
    Maximum quantity 64 64 64 64
    Compressor Type DC inverter
    Quantity 1
    Oil type FV68H
    Start-up method Soft start
    Fan Type Propeller
    Motor type DC
    Quantity 2
    Motor output kW 0.92×2 0.92×2 0.92×2 0.92×2
    Static pressure Pa 0,20,40,60,80(Selectable)
    Air flow rate m3/h 14000 14900 15800 15800
    Drive type Direct
    Refrigerant Type R410A
    Factory charge kg 10 10 10 10
    Pipe connections4 Liquid pipe mm Φ15.9 Φ15.9 Φ15.9 Φ15.9
    Low pressure gas mm Φ28.6 Φ28.6 Φ28.6 Φ28.6
    High pressure gas mm Φ22.2 Φ22.2 Φ22.2 Φ22.2
    Sound pressure level5 dB(A) 61 64 65 65
    Sound power level5 dB(A) 81 88 88 88
    Net dimensions (W×H×D) mm 1340×1635×825 1340×1635×825 1340×1635×825 1340×1635×825
    Packed dimensions (W×H×D) mm 1405×1805×910 1405×1805×910 1405×1805×910 1405×1805×910
    Net weight kg 300 300 300 300
    Gross weight kg 325 325 325 325
    Ambient temp. operation range Cooling6 oC(DB) -15 ~ 52
    Heating oC(WB) -25 ~ 19
    Domestic hot water oC(DB) -20 ~ 43
    Notes:            
    1.     Indoor air temperature 27°C DB, 19°C WB; outdoor air temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
    2.     Indoor air temperature 20°C DB; outdoor air temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
    3.     Refer to table 1-5.1: Indoor and outdoor unit combination ratio limitations in Part 1.    
    4.     Diameters given are those of the unit's stop valve.        
    5.     Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.  
    6.     -15°C to -5°C low temperature cooling operation is just available for MS01.      
    HP 22 24 26
    Model name MV6-R615WV2GN1 MV6-R680WV2GN1 MV6-R735WV2GN1
    Combination type 10HP+12HP 10HP+14HP 12HP+14HP
    Power supply V/N/Hz 380-415/3/50(60)
    Cooling1 Capacity kW 61.5 68 73.5
    Power input kW 15.82 17.01 18.46
    EER 3.89 4.00 3.98
    Heating2(Rated) Capacity kW 61.5 68 73.5
    Power input kW 12.03 13.72 14.83
    COP 5.11 4.96 4.96
    Heating2(Max) Capacity kW 69.00 76.50 82.5
    Power input kW 16.60 16.90 19.27
    COP 4.16 4.53 4.28
    Connected    indoor
    unit
    Total capacity 50-200% of outdoor unit capacity3
    Maximum quantity 64 64 64
    Compressor Type DC inverter
    Quantity 2
    Oil type FV68H
    Start-up method Soft start
    Fan Type Propeller
    Motor type DC
    Quantity 2 2 3
    Motor output kW 0.92×2 0.92×3 0.92×3
    Static pressure Pa 0,20,40,60,80(Selectable)
    Air flow rate m3/h 19500 23500 24000
    Drive type Direct
    Refrigerant Type R410A
    Factory charge kg 16 18 18
    Pipe connections4 Liquid pipe mm Φ15.9 Φ15.9 Φ19.1
    Low pressure gas mm Φ28.6 Φ34.9 Φ34.9
    High pressure gas mm Φ28.6 Φ28.6 Φ28.6
    Sound pressure level5 dB(A) 62 63 64
    Sound power level5 dB(A) 83 83 84
    Net dimensions (W×H×D) mm (990×1635×790)×2 990×1635×790+
    1340×1635×825
    990×1635×790+
    1340×1635×825
    Packed dimensions (W×H×D) mm (1090×1805×860)×2 1090×1805×860+
    1405×1805×910
    1090×1805×860+
    1405×1805×910
    Net weight kg 232×2 232+300 232+300
    Gross weight kg 248×2 248+325 248+325
    Ambient temp. operation range Cooling6 oC(DB) -15 ~ 52
    Heating oC(WB) -25 ~ 19
    Domestic hot water oC(DB) -20 ~ 43
    Notes:          
    1.     Indoor air temperature 27°C DB, 19°C WB; outdoor air temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
    2.     Indoor air temperature 20°C DB; outdoor air temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
    3.     Refer to table 1-5.1: Indoor and outdoor unit combination ratio limitations in Part 1.    
    4.     Diameters given are those for the pipe connecting the outdoor unit combination to the first indoor branch joint for systems with total equivalent liquid piping lengths of less than 90m. For systems with total equivalent liquid piping lengths of 90m or longer, please refer to Part 3 “System Design and Installation” for connection piping diameters.
    5.     Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.
    6.     -15°C to -5°C low temperature cooling operation is just available for MS01.    
    HP 28 30 32
    Model name MV6-R785WV2GN1 MV6-R835WV2GN1 MV6-R900WV2GN1
    Combination type 12HP+16HP 12HP+18HP 16HP+16HP
    Power supply V/N/Hz 380-415/3/50(60)
    Cooling1 Capacity kW 78.5 83.5 90
    Power input kW 20.64 22.45 24.00
    EER 3.80 3.72 3.75
    Heating2(Rated) Capacity kW 78.5 83.5 90
    Power input kW 16.35 18.47 19.57
    COP 4.80 4.52 4.60
    Heating2(Max) Capacity kW 87.5 93.5 100
    Power input kW 21.74 24.25 24.52
    COP 4.02 3.86 4.08
    Connected
    indoor unit
    Total capacity 50-200% of outdoor unit capacity3
    Maximum quantity 64 64 64
    Compressor Type DC inverter
    Quantity 2
    Oil type FV68H
    Start-up method Soft start
    Fan Type Propeller
    Motor type DC
    Quantity 3 3 4
    Motor output kW 0.92×3 0.92×3 0.92×4
    Static pressure Pa 0,20,40,60,80(Selectable)
    Air flow rate m3/h 24900 25800 29800
    Drive type Direct
    Refrigerant Type R410A
    Factory charge kg 18 18 20
    Pipe connections4 Liquid pipe mm Φ19.1 Φ19.1 Φ19.1
    Low pressure gas pipe mm Φ34.9 Φ34.9 Φ34.9
    High pressure gas pipe mm Φ28.6 Φ28.6 Φ28.6
    Sound pressure level5 dB(A) 65 66 67
    Sound power level5 dB(A) 89 89 91
    Net dimensions (W×H×D) mm 990×1635×790+
    1340×1635×825
    990×1635×790+
    1340×1635×825
    (1340×1635×825)×2
    Packed dimensions (W×H×D) mm 1090×1805×860+
    1405×1805×910
    1090×1805×860+
    1405×1805×910
    (1405×1805×910)×2
    Net weight kg 232+300 232+300 300×2
    Gross weight kg 248+325 248+325 325×2
    Ambient temp. operation range Cooling6 oC(DB) -15 ~ 52
    Heating oC(WB) -25 ~ 19
    Domestic hot water oC(DB) -20 ~ 43
    Notes:          
    1.     Indoor air temperature 27°C DB, 19°C WB; outdoor air temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
    2.     Indoor air temperature 20°C DB; outdoor air temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
    3.     Refer to table 1-5.1: Indoor and outdoor unit combination ratio limitations in Part 1.    
    4.     Diameters given are those for the pipe connecting the outdoor unit combination to the first indoor branch joint for systems with total equivalent liquid piping lengths of less than 90m. For systems with total equivalent liquid piping lengths of 90m or longer, please refer to Part 3 “System Design and Installation” for connection piping diameters.
    5.     Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.
    6.     -15°C to -5°C low temperature cooling operation is just available for MS01.    
               
    HP 34 36 38
    Model name MV6-R950WV2GN1 MV6-R1000WV2GN1 MV6-R1060WV2GN1
    Combination type 16HP+18HP 18HP+18HP 18HP+20HP
    Power supply V/N/Hz 380-415/3/50(60)
    Cooling1 Capacity kW 95 100 106
    Power input kW 25.81 27.62 31.20
    EER 3.68 3.62 3.40
    Heating2(Rated) Capacity kW 95 100 106
    Power input kW 21.69 23.81 26.67
    COP 4.38 4.20 3.97
    Heating2(Max) Capacity kW 106 112 119
    Power input kW 27.03 29.53 33.09
    COP 3.92 3.79 3.60
    Connected  indoor
    unit
    Total capacity 50-200% of outdoor unit capacity3
    Maximum quantity 64 64 64
    Compressor Type DC inverter
    Quantity 2
    Oil type FV68H
    Start-up method Soft start
    Fan Type Propeller
    Motor type DC
    Quantity 4
    Motor output kW 0.92×4 0.92×4 0.92×4
    Static pressure Pa 0,20,40,60,80(Selectable)
    Air flow rate m3/h 30700 31600 31600
    Drive type Direct
    Refrigerant Type R410A
    Factory charge kg 20 20 20
    Pipe connections4 Liquid pipe mm Φ19.1 Φ19.1 Φ19.1
    Low pressure gas mm Φ34.9 Φ34.9 Φ41.3
    High pressure gas mm Φ28.6 Φ28.6 Φ34.9
    Sound pressure level5 dB(A) 68 68 68
    Sound power level5 dB(A) 91 91 91
    Net dimensions (W×H×D) mm (1340×1635×825)×2 (1340×1635×825)×2 (1340×1635×825)×2
    Packed dimensions (W×H×D) mm (1405×1805×910)×2 (1405×1805×910)×2 (1405×1805×910)×2
    Net weight kg 300×2 300×2 300×2
    Gross weight kg 325×2 325×2 325×2
    Ambient temp. operation range Cooling6 oC(DB) -15 ~ 52
    Heating oC(WB) -25 ~ 19
    Domestic hot water oC(DB) -20 ~ 43
    Notes:          
    1.     Indoor air temperature 27°C DB, 19°C WB; outdoor air temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
    2.     Indoor air temperature 20°C DB; outdoor air temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
    3.     Refer to table 1-5.1: Indoor and outdoor unit combination ratio limitations in Part 1.    
    4.     Diameters given are those for the pipe connecting the outdoor unit combination to the first indoor branch joint for systems with total equivalent liquid piping lengths of less than 90m. For systems with total equivalent liquid piping lengths of 90m or longer, please refer to Part 3 “System Design and Installation” for connection piping diameters.
    5.     Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.
    6.     -15°C to -5°C low temperature cooling operation is just available for MS01.    
    HP 40 42 44
    Model name MV6-R1120WV2GN1 MV6-R1185WV2GN1 MV6-R1235WV2GN1
    Combination type 20HP+20HP 12HP+14HP+16HP 12HP+16HP+16HP
    Power supply V/N/H 380-415/3/50(60)
    Cooling1 Capacity kW 112 118.5 123.5
    Power input kW 34.78 30.46 32.64
    EER 3.22 3.89 3.78
    Heating2(Rated) Capacity kW 112 118.5 123.5
    Power input kW 29.53 24.62 26.13
    COP 3.79 4.81 4.73
    Heating2(Max) Capacity kW 126 132.5 137.5
    Power input kW 36.65 31.53 34.01
    COP 3.44 4.20 4.04
    Connected
    indoor unit
    Total capacity 50-200% of outdoor unit capacity3
    Maximum quantity 64 64 64
    Compressor Type DC inverter
    Quantity 2 3 3
    Oil type FV68H
    Start-up method Soft start
    Fan Type Propeller
    Motor type DC
    Quantity 4 5 5
    Motor output kW 0.92×4 0.92×5 0.92×5
    Static pressure Pa 0,20,40,60,80(Selectable)
    Air flow rate m3/h 31600 38900 39800
    Drive type Direct
    Refrigerant Type R410A
    Factory charge kg 20 28 28
    Pipe connections4 Liquid pipe mm Φ19.1 Φ19.1 Φ19.1
    Low pressure gas mm Φ41.3 Φ41.3 Φ41.3
    High pressure gas mm Φ34.9 Φ34.9 Φ34.9
    Sound pressure level5 dB(A) 68 67 68
    Sound power level5 dB(A) 91 89 91
    Net dimensions (W×H×D) mm (1340×1635×825)×2 990×1635×790+ (1340×1635×825)×2 990×1635×790+ (1340×1635×825)×2
    Packed dimensions (W×H×D) mm (1405×1805×910)×2 1090×1805×860+ (1405×1805×910)×2 1090×1805×860+ (1405×1805×910)×2
    Net weight kg 300×2 232+300×2 232+300×2
    Gross weight kg 325×2 248+325×2 248+325×2
    Ambient temp. operation range Cooling6 oC(DB) -15 ~ 52
    Heating oC(WB -25 ~ 19
    Domestic hot water oC(DB) -20 ~ 43
    Notes:          
    1. Indoor air temperature 27°C DB, 19°C WB; outdoor air temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
    2. Indoor air temperature 20°C DB; outdoor air temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
    3. Refer to table 1-5.1: Indoor and outdoor unit combination ratio limitations in Part 1.  
    4. Diameters given are those for the pipe connecting the outdoor unit combination to the first indoor branch joint for systems with total equivalent liquid piping lengths of less than 90m. For systems with total equivalent liquid piping lengths of 90m or longer, please refer to Part 3 “System Design and Installation” for connection piping diameters.
    5. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.
    6. -15°C to -5°C low temperature cooling operation is just available for MS01.    
    HP 46 48 50
    Model name MV6-R1300WV2GN1 MV6-R1350WV2GN1 MV6-R1400WV2GN1
    Combination type 14HP+16HP+16HP 16HP+16HP+16HP 16HP+16HP+18HP
    Power supply V/N/Hz 380-415/3/50(60)
    Cooling1 Capacity kW 130 135 140
    Power input kW 33.83 36.00 37.81
    EER 3.84 3.75 3.70
    Heating2(Rated) Capacity kW 130 135 140
    Power input kW 27.83 29.35 31.47
    COP 4.67 4.60 4.45
    Heating2(Max) Capacity kW 145 150 156
    Power input kW 34.31 36.79 39.29
    COP 4.23 4.08 3.97
    Connected
    indoor unit
    Total capacity 50-200% of outdoor unit capacity3
    Maximum quantity 64 64 64
    Compressor Type DC inverter
    Quantity 3
    Oil type FV68H
    Start-up method Soft start
    Fan Type Propeller
    Motor type DC
    Quantity 6 6 6
    Motor output kW 0.92×6 0.92×6 0.92×6
    Static pressure Pa 0,20,40,60,80(Selectable)
    Air flow rate m3/h 43800 44700 45600
    Drive type Direct
    Refrigerant Type R410A
    Factory charge kg 30 30 30
    Pipe connections4 Liquid pipe mm Φ19.1 Φ19.1 Φ19.1
    Low pressure gas pipe mm Φ41.3 Φ41.3 Φ41.3
    High pressure gas mm Φ34.9 Φ34.9 Φ34.9
    Sound pressure level5 dB(A) 68 69 69
    Sound power level5 dB(A) 91 93 93
    Net dimensions (W×H×D) mm (1340×1635×825)×3 (1340×1635×825)×3 (1340×1635×825)×3
    Packed dimensions (W×H×D) mm (1405×1805×910)×3 (1405×1805×910)×3 (1405×1805×910)×3
    Net weight kg 300×3 300×3 300×3
    Gross weight kg 325×3 325×3 325×3
    Ambient temp. operation
    range
    Cooling6 oC(DB) -15 ~ 52
    Heating oC(WB) -25 ~ 19
    Domestic hot water oC(DB) -20 ~ 43
    Notes:          
    1.     Indoor air temperature 27°C DB, 19°C WB; outdoor air temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
    2.     Indoor air temperature 20°C DB; outdoor air temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
    3.     Refer to table 1-5.1: Indoor and outdoor unit combination ratio limitations in Part 1.    
    4.    Diameters given are those for the pipe connecting the outdoor unit combination to the first indoor branch joint for systems with total equivalent liquid piping lengths of less than 90m. For systems with total equivalent liquid piping lengths of 90m or longer, please refer to Part 3 “System Design and Installation” for connection piping diameters.
    5.     Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.
    6.     -15°C to -5°C low temperature cooling operation is just available for MS01.    
    HP 52 54 56
    Model name MV6-R1450WV2GN1 MV6-R1500WV2GN1 MV6-R1560WV2GN1
    Combination type 16HP+18HP+18HP 18HP+18HP+18HP 18HP+18HP+20HP
    Power supply V/N/Hz 380-415/3/50(60)
    Cooling1 Capacity kW 145 150 156
    Power input kW 39.62 41.44 45.01
    EER 3.66 3.62 3.47
    Heating2(Rated) Capacity kW 145 150 156
    Power input kW 33.59 35.71 38.58
    COP 4.32 4.20 4.04
    Heating2(Max) Capacity kW 162 168 175
    Power input kW 41.80 44.30 47.86
    COP 3.97 3.88 3.79
    Connected  indoor
    unit
    Total capacity 50-200% of outdoor unit capacity3
    Maximum quantity 64 64 64
    Compressor Type DC inverter
    Quantity 3
    Oil type FV68H
    Start-up method Soft start
    Fan Type Propeller
    Motor type DC
    Quantity 6 6 6
    Motor output kW 0.92×6 0.92×6 0.92×6
    Static pressure Pa 0,20,40,60,80(Selectable)
    Air flow rate m3/h 46500 47400 47400
    Drive type Direct
    Refrigerant Type R410A
    Factory charge kg 30 30 30
    Pipe connections4 Liquid pipe mm Φ19.1 Φ19.1 Φ19.1
    Low pressure gas mm Φ41.3 Φ41.3 Φ41.3
    High pressure gas mm Φ34.9 Φ34.9 Φ34.9
    Sound pressure level5 dB(A) 69 70 70
    Sound power level5 dB(A) 93 93 93
    Net dimensions (W×H×D) mm (1340×1635×825)×3 (1340×1635×825)×3 (1340×1635×825)×3
    Packed dimensions (W×H×D) mm (1405×1805×910)×3 (1405×1805×910)×3 (1405×1805×910)×3
    Net weight kg 300×3 300×3 300×3
    Gross weight kg 325×3 325×3 325×3
    Ambient temp. operation range Cooling6 oC(DB) -15 ~ 52
    Heating oC(WB) -25 ~ 19
    Domestic hot oC(DB) -20 ~ 43
    Notes:          
    1.     Indoor air temperature 27°C DB, 19°C WB; outdoor air temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
    2.     Indoor air temperature 20°C DB; outdoor air temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
    3.     Refer to table 1-5.1: Indoor and outdoor unit combination ratio limitations in Part 1.    
    4.     Diameters given are those for the pipe connecting the outdoor unit combination to the first indoor branch joint for systems with total equivalent liquid piping lengths of less than 90m. For systems with total equivalent liquid piping lengths of 90m or longer, please refer to Part 3 “System Design and Installation” for connection piping diameters.
    5.     Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.
    6.     -15°C to -5°C low temperature cooling operation is just available for MS01.    
    HP 58 60
    Model name MV6-R1620WV2GN1 MV6-R1680WV2GN1
    Combination type 18HP+20HP+20HP 20HP+20HP+20HP
    Power supply V/N/Hz 380-415/3/50(60)
    Cooling1 Capacity kW 162 168
    Power input kW 48.59 52.17
    EER 3.33 3.22
    Heating2(Rated) Capacity kW 162 168
    Power input kW 41.44 44.30
    COP 3.91 3.79
    Heating2(Max) Capacity kW 182 189
    Power input kW 51.42 54.98
    COP 3.54 3.44
    Connected indoor unit Total capacity 50-200% of outdoor unit capacity
    Maximum quantity 64 64
    Compressor Type DC inverter
    Quantity 3
    Oil type FV68H
    Start-up method Soft start
    Fan Type Propeller
    Motor type DC
    Quantity 6 6
    Motor output kW 0.92×6 0.92×6
    Static pressure Pa 0,20,40,60,80(Selectable)
    Air flow rate m3/h 47400 47400
    Drive type Direct
    Refrigerant Type R410A
    Factory charge kg 30 30
    Pipe connections3 Liquid pipe mm Φ19.1 Φ19.1
    Low pressure gas pipe mm Φ41.3 Φ41.3
    High pressure gas pipe mm Φ34.9 Φ34.9
    Sound pressure level4 dB(A) 70 70
    Sound power level4 dB(A) 93 93
    Net dimensions (W×H×D) mm (1340×1635×825)×3 (1340×1635×825)×3
    Packed dimensions (W×H×D) mm (1405×1805×910)×3 (1405×1805×910)×3
    Net weight kg 300×3 300×3
    Gross weight kg 325×3 325×3
    Ambient temp. operation range Cooling oC(DB) -15 ~ 52
    Heating oC(WB) -25 ~ 19
    Domestic hot water oC(DB) -20 ~ 43
    Notes:        
    1.     Indoor air temperature 27°C DB, 19°C WB; outdoor air temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
    2.     Indoor air temperature 20°C DB; outdoor air temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
    3.     Refer to table 1-5.1: Indoor and outdoor unit combination ratio limitations in Part 1.  
    4.     Diameters given are those for the pipe connecting the outdoor unit combination to the first indoor branch joint for systems with total equivalent liquid piping lengths of less than 90m. For systems with total equivalent liquid piping lengths of 90m or longer, please refer to Part 3 “System Design and Installation” for connection piping diameters.
    5.     Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.
    6.     -15°C to -5°C low temperature cooling operation is just available for MS01.    
    Model name MS01/N1-D1 MS04/N1-D MS06/N1-D
    Power supply V/ph/Hz 220-240/1/50(60)    
    Max. number of indoor unit groups 1 4 6
    Max. number of units per group 8 5 5
    Max. number of downstream indoor units 8 20 30
    Max. capacity of each group of indoor units kW 32 16 16
    Total capacity of downstream indoor units kW 32 49 63
    Pipe connections
    to ODU
    Liquid pipe mm ∅9.53/∅12.7 ∅9.53/∅12.7/∅15.9/∅19.05 ∅9.53/∅12.7/∅15.9/∅19.05
    Low pressure gas
    pipe
    mm ∅15.9/∅19.1/∅22.2 ∅19.1/∅22.2/∅28.6 ∅19.1/∅22.2/∅28.6
    High pressure gas pipe mm ∅12.7/∅15.9/∅19.1 ∅15.9/∅19.1/∅22.2/∅28.6 ∅15.9/∅19.1/∅22.2/∅28.6
    Pipe connections
    to IDU
    Liquid pipe mm ∅6.35/∅9.53 ∅6.35/∅9.53 ∅6.35/∅9.53
    Gas pipe mm ∅12.7/∅15.9 ∅12.7/∅15.9 ∅12.7/∅15.9
    Sound pressure level2 dB(A) 40 44 45
    Sound power level2 dB(A) 60 63 65
    Net dimensions (W×H×D) mm 440×195×296 668×250×574 668×250×574
    Packed dimensions (W×H×D) mm 740×275×405 1020×390×850 1020×390×850
    Net weight kg 10.5 33 36
    Gross weight kg 14 58 61
    Notes:          
    1.     MS01 is for low temperature cooling operation and leakage detection.    
    2.     The sound level is measured at a position 1m below the MS box in a semi-anechoic chamber whilst the MS box is switching mode. MS box should not be installed in locations with low-noise requirements.
    Model name MS08/N1-D MS10/N1-D MS12/N1-D
    Power supply V/ph/Hz 220-240/1/50(60)
    Max. number of indoor unit groups 8 10 12
    Max. number of units per group 5 5 5
    Max. number of downstream indoor units 40 47 47
    Max.  capacity  of  each  group  of indoor units kW 16 16 16
    Total    capacity    of    downstream indoor units kW 85 85 85
    Pipe  connections
    to ODU
    Liquid pipe mm ∅12.7/∅15.9/∅19.1/∅22.2 ∅12.7/∅15.9/∅19.1/∅22.2 ∅12.7/∅15.9/∅19.1/∅22.2
    Low pressure gas
    pipe
    mm ∅22.2/∅28.6/∅34.9 ∅22.2/∅28.6/∅34.9 ∅22.2/∅28.6/∅34.9
    High pressure gas pipe mm ∅19.1/∅22.2/∅28.6 ∅19.1/∅22.2/∅28.6 ∅19.1/∅22.2/∅28.6
    Pipe  connections
    to IDU
    Liquid pipe mm ∅6.35/∅9.53 ∅6.35/∅9.53 ∅6.35/∅9.53
    Gas pipe mm ∅12.7/∅15.9 ∅12.7/∅15.9 ∅12.7/∅15.9
    Sound pressure level1 dB(A) 47 47 47
    Sound power level1 dB(A) 65 65 65
    Net dimensions (W×H×D) mm 974×250×574 974×250×574 974×250×574
    Packed dimensions (W×H×D) mm 1320×390×850 1320×390×850 1320×390×850
    Net weight kg 48 51 54
    Gross weight kg 79 82 85
    Notes:          
    1.        The sound level is measured at a position 1m below the MS box in a semi-anechoic chamber whilst the MS box is switching mode. MS box should not be installed in locations with low-noise requirements.