Operating ambient temperatures
Suggested retail price
Technology
Blue Fin
Blue fin heat exchanger cover - Protection against corrosion. Special anti-corrosion coating of the heat exchanger, protection from atmospheric phenomena and effects of aggressive environment. May differ in color (have blue, green, gold or no color at all (clear varnish)
Compresor DC inverter
Compressor with inverter DC can increase the efficiency of the air conditioner, thus reducing power consumption saves your costs. This system is much more economical and safer than air conditioners with a constant output of the compressor.
DC inverter motor Outdoor Unit
In outdoor units, a DC motor is used to rotate the fan. This allows you to significantly reduce noise and power consumption. And also get several positions of the fan speed, depending on the needs of the system.
Multi-Bend Heat Exchanger
Increased heat. This unit uses the heat exchangers with tubes of a special design, the inner surface of which has trapezoidal notches "Innergrove cooper", which provides maximum heat transfer surface area increased. Due to this heat increases by 28%, reduced power consumption, and hence increases the efficiency of the system.
Outdoor unit design "Brilliant"
Designers Midea did not forget about the exterior of the exterior unit of the air conditioner, which in itself is a rarity for climate technology. The outdoor unit is much more elegant than its counterparts, it has facets like a diamond, and attention to detail speaks of a high level of production and a carefully thought-out design concept.
Sine-Wave Inverter
Technology 180° -gradusnogo wave inverter conversion - control voltage without the "pulse" effects (jagged sinusoid).
Compared with the current standard of 120° rectangular wave has the following advantages:
- Ability to work with a wider range of supply voltage and frequency.
- Most of the energy efficiency and energy conservation.
- More soft start, lower noise and vibration.
- more control.
Description
• 13 basic outdoor units with a capacity of 25.2 ~ 90 kW, without the possibility of combining.
• Modern outdoor units Full DC-Inverter with EVI technology, operation for heating at a temperature of -25°C outside air.
• Freon cooling of the power control module for compressors.
• Subcooling by means of an additional plate heat exchanger.
• All compressors - Hitachiat exchanger.
• All compressors - Hitachi
• Advanced microprocessor control.
• Intelligent defrost cycle during heating operation.
• Improved oil return program (no oil return loops required).
• The total capacity of indoor units can be up to 130% of the capacity of the outdoor unit.
• Can be used in buildings of all sizes, civil engineering and commercial real estate.
• Automatic addressing of indoor units.
• From 2021, they will be equipped with a Black Box board for accumulating diagnostic data.
Specifications
HP | 8 | 10 | 12 | 14 | ||
Model name | MV6-i252WV2GN1-E | MV6-i280WV2GN1-E | MV6-i335WV2GN1-E | MV6-i400WV2GN1-E | ||
Power supply | V/Ph/Hz | 380-415/3/50 | ||||
Cooling1 | Capacity | kW | 25.2 | 28.0 | 33.5 | 40.0 |
kBtu/h | 86.0 | 95.5 | 114.3 | 136.5 | ||
Power input | kW | 5.5 | 6.7 | 8.9 | 11.0 | |
EER | 4.55 | 4.20 | 3.75 | 3.65 | ||
Heating2 | Capacity | kW | 25.2 | 28.0 | 33.5 | 40.0 |
kBtu/h | 86.0 | 95.5 | 114.3 | 136.5 | ||
Power input | kW | 4.8 | 5.5 | 7.6 | 9.3 | |
COP | 5.20 | 5.10 | 4.40 | 4.30 | ||
Connected indoor unit |
Total capacity | 50-130% of outdoor unit capacity | ||||
Maximum quantity | 13 | 16 | 20 | 23 | ||
Compressor | Type | DC inverter | ||||
Quantity | 1 | |||||
Oil type | FV68H | |||||
Start-up method | Soft start | |||||
Fan | Type | Propeller | ||||
Motor type | DC | |||||
Quantity | 1 | |||||
Motor output | kW | 0.56 | 0.56 | 0.56 | 0.92 | |
Airflow rate | m3/h | 11000 | 11000 | 11000 | 13000 | |
Drive type | Direct | |||||
Refrigerant | Type | R410A | ||||
Factory charge | kg | 11 | 11 | 11 | 13 | |
Pipe connections3 |
Liquid pipe | mm | Φ12.7 | Φ15.9 | Φ15.9 | |
Gas pipe | mm | Φ25.4 | Φ28.6 | Φ31.8 | ||
Sound pressure level4 | dB(A) | 58 | 60 | 62 | ||
Sound power level | dB(A) | 78 | 81 | 85 | ||
Net dimensions (W×H×D) | mm | 990×1635×790 | 1340×1635×850 | |||
Packed dimensions (W×H×D) | mm | 1090×1805×860 | 1405×1805×910 | |||
Net weight | kg | 227 | 277 | |||
Gross weight | kg | 242 | 304 | |||
Ambient temp. operation range |
Cooling | oC | -5 ~ 48 | |||
Heating | oC | -25 ~ 24 | ||||
Notes: | ||||||
1. Indoor air temperature 27°C DB, 19°C WB; outdoor air temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference. | ||||||
2. Indoor air temperature 20°C DB; outdoor air temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference. | ||||||
3. Diameters given are those of the unit's stop valve. | ||||||
4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber. |
HP | 16 | 18 | 20 | 22 | ||
Model name | MV6-i450WV2GN1-E | MV6-i500WV2GN1-E | MV6-i560WV2GN1-E | MV6-i615WV2GN1-E | ||
Power supply | V/Ph/Hz | 380-415/3/50 | ||||
Cooling1 | Capacity | kW | 45.0 | 50.0 | 56.0 | 61.5 |
kBtu/h | 153.5 | 170.6 | 191.1 | 209.8 | ||
Power input | kW | 12.9 | 14.7 | 16.0 | 20.2 | |
EER | 3.50 | 3.40 | 3.50 | 3.05 | ||
Heating2 | Capacity | kW | 45.0 | 50.0 | 56.0 | 61.5 |
kBtu/h | 153.5 | 170.6 | 191.1 | 209.8 | ||
Power input | kW | 10.7 | 12.2 | 13.8 | 17.6 | |
COP | 4.20 | 4.10 | 4.05 | 3.50 | ||
Connected indoor unit |
Total capacity | 50-130% of outdoor unit capacity | ||||
Maximum quantity | 26 | 29 | 33 | 36 | ||
Compressor | Type | DC inverter | ||||
Quantity | 1 | 2 | ||||
Oil type | FV68H | |||||
Start-up method | Soft start | |||||
Fan | Type | Propeller | ||||
Motor type | DC | |||||
Quantity | 1 | 2 | ||||
Motor output | kW | 0.92 | 0.92 | 0.56×2 | 0.56×2 | |
Airflow rate | m3/h | 13000 | 13000 | 17000 | 17000 | |
Drive type | Direct | |||||
Refrigerant | Type | R410A | ||||
Factory charge | kg | 13 | 13 | 17 | 17 | |
Pipe connections3 |
Liquid pipe | mm | Φ15.9 | Φ19.1 | ||
Gas pipe | mm | Φ31.8 | Φ31.8 | |||
Sound pressure level4 | dB(A) | 65 | 66 | |||
Sound power level | dB(A) | 88 | ||||
Net dimensions (W×H×D) | mm | 1340×1635×850 | 1340×1635×825 | |||
Packed dimensions (W×H×D) | mm | 1405×1805×910 | ||||
Net weight | kg | 277 | 295 | 344 | 344 | |
Gross weight | kg | 304 | 322 | 364 | 364 | |
Ambient temp. operation range |
Cooling | oC | -5 ~ 48 | |||
Heating | oC | -25 ~ 24 | ||||
Notes: | ||||||
1. Indoor air temperature 27°C DB, 19°C WB; outdoor air temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference. | ||||||
2. Indoor air temperature 20°C DB; outdoor air temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference. | ||||||
3. Diameters given are those of the unit's stop valve. | ||||||
4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber. |
HP | 24 | 26 | 28 | 30 | ||
Model name | MV6-i670WV2GN1-E | MV6-i730WV2GN1-E | MV6-i785WV2GN1-E | MV6-i850WV2GN1-E | ||
Power supply | V/Ph/Hz | 380-415/3/50 | ||||
Cooling1 | Capacity | kW | 67.0 | 73.0 | 78.5 | 85.0 |
kBtu/h | 228.6 | 249.1 | 267.8 | 290.0 | ||
Power input | kW | 21.6 | 21.6 | 24.9 | 28.3 | |
EER | 3.10 | 3.40 | 3.15 | 3.00 | ||
Heating2 | Capacity | kW | 67.0 | 73.0 | 78.5 | 85.0 |
kBtu/h | 228.6 | 249.1 | 267.8 | 290.0 | ||
Power input | kW | 16.8 | 18.1 | 21.8 | 24.3 | |
COP | 4.00 | 4.05 | 3.60 | 3.50 | ||
Connected indoor unit |
Total capacity | 50-130% of outdoor unit capacity | ||||
Maximum quantity | 39 | 43 | 46 | 50 | ||
Compressor | Type | DC inverter | ||||
Quantity | 2 | |||||
Oil type | FV68H | |||||
Start-up method | Soft start | |||||
Fan | Type | Propeller | ||||
Motor type | DC | |||||
Quantity | 2 | |||||
Motor output | kW | 0.92×2 | 0.92×2 | 0.92×2 | 0.92×2 | |
Airflow rate | m3/h | 25000 | 25000 | 25000 | 24000 | |
Drive type | Direct | |||||
Refrigerant | Type | R410A | ||||
Factory charge | kg | 22 | 22 | 22 | 25 | |
Pipe connections3 |
Liquid pipe | mm | Φ19.1 | Φ22.2 | Φ22.2 | |
Gas pipe | mm | Φ31.8 | Φ31.8 | Φ38.1 | ||
Sound pressure level4 | dB(A) | 67 | 68 | |||
Sound power level | dB(A) | 89 | 90 | |||
Net dimensions (W×H×D) | mm | 1730×1830×850 | ||||
Packed dimensions (W×H×D) | mm | 1800×2000×910 | ||||
Net weight | kg | 407 | 429 | 475 | ||
Gross weight | kg | 430 | 452 | 507 | ||
Ambient temp. operation range |
Cooling | oC | -5 ~ 48 | |||
Heating | oC | -25 ~ 24 | ||||
Notes: | ||||||
1. Indoor air temperature 27°C DB, 19°C WB; outdoor air temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference. | ||||||
2. Indoor air temperature 20°C DB; outdoor air temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference. | ||||||
3. Diameters given are those of the unit's stop valve. | ||||||
4. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber. |