Midea "Indoor units MDV of high Static Pressure Duct T1N1-B(B) series"

Suggested retail price

45,100- ... 200,900-hrv.

    Central Controller

    1. The central controller is used for centralized management of indoor units (up to 64 indoor units can be connected via an adapter card).
    2. The indoor units can be divided into 20 zones, each zone can contain no more than 64 indoor units. All indoor units in one zone can only be set to the same mode. (By default, "the zone is not assigned to indoor units").
    3. Users can select the desired mode and temperature with a weekly schedule.

    Dry Mode

    Dry mode automatically selects cooling, based on the difference between fixed and temparaturoy actual room temperature. The temperature is regulated while reducing humidity repeated switching on and off of the cooling and ventilation only. when the dry mode on the remote control shows "Drop"

    Multi-Bend Heat Exchanger

    Increased heat. This unit uses the heat exchangers with tubes of a special design, the inner surface of which has trapezoidal notches "Innergrove cooper", which provides maximum heat transfer surface area increased. Due to this heat increases by 28%, reduced power consumption, and hence increases the efficiency of the system.

    Temperature compensation

    The function of temperature compensation corrects the temperature in the person's zone of being comfortable, (because the air temperature near the floor and ceiling can differ by several degrees) by further increasing / decreasing the temperature from the value set from the remote control. Thus, compensation and equalization of the overall room temperature occurs. For household split systems, the value is set by the manufacturer and is 2°C.

    • Designed for mounting in a suspended ceiling with a connection to the airway branched networks and / or the high points in the blowing - up to 7 m above the floor;
    • Flanges air intake channel - on the rear wall of the blocks;
    • The ability to organize mix with fresh air;
    • Remote control and photodetector as standard;
    • Air pressure 60-150 Pa at the operating point 196 or 280Pa - maximum.
    Model MDV-D71T1/N1-B(B) MDV-D80T1/N1-B(B) MDV-D90T1/N1-B(B)
    Power supply V- Ph-Hz 220-240V~, 1Ph, 50Hz
    Cooling Capacity kW 7.1 8.0 9.0
    Input W 263 263 423
    Rated current A 1.23 1.23 1.87
    Heating Capacity kW 8.0 9.0 10.0
    Input W 263 263 423
    Rated current A 1.23 1.23 1.87
    Max. input consumption W 269 269 437
    Max. current A 1.23 1.23 1.87
    Indoor
    fan motor
    Model YDK100-4X-2 YDK100-4X-2 YDK160-4C
    Type AC Motor
    Brand Yong An Yong An WELLING
    Input W 240 240 375
    Capacitor μF 12 12 10
    Speed (h/m/l) r/min 990/940/900 990/940/900 1335/1290/1235
    Indoor coil Number of rows 2 2 3
    Tube pitch(a) × row pitch(b) mm 25.4×22 25.4×22 25.4×22
    Fin spacing mm 1.5 1.5 1.6
    Fin type Hydrophilic aluminum
    Tube outside diameter and
    type
    mm Ф9.52
    inner groove tube
    length× height× width mm 700×356×44 700×356×44 700×356×66
    Number of circuits 3 3 7
    Indoor air flow (H/M/L) m3/h 1443/1361/1218 1416/1338/1220 1951/1741/1518
    *Indoor external static pressure Pa 25(25~ 196) 37(37~ 196) 37(37~ 196)
    Indoor noise level (H/M/L) dB(A) 48/46/44 48/46/44.5 52/49/47
    Indoor unit Dimension (W×H×D) mm 952×420×690 952×420×690 952×420×690
    Packing (W×H×D) mm 1090×440×768 1090×440×768 1090×440×768
    Net/Gross weight kg 45/50 45/50 46.5/52.4
    Refrigerant type R410A
    Throttle Type Electronic expansion valve
    Model BD20FKS (Winding: DZF20XQ-1000-XHP-6)
    Design pressure (H/L) MPa 4.4/2.6
    Refrigerant piping Liquid / Gas mm Ф9.53/ Ф15.9 Ф9.53/ Ф15.9 Ф9.53/ Ф15.9
    Connecting wiring Power wiring mm2 3×2.5(L20m); 3×3.5(L50m)
    Signal wiring mm2 3×0.75
    Drainage water pipe diameter OD Ф25
    Controller Wired controller KJR-29B1/BK-E (6 meters connection wire)
    Model MDV-D112T1/N1-B(B) MDV-D140T1/N1-B(B) MDV-D160T1/N1-B(B)
    Power supply V- Ph-Hz 220-240V~, 1Ph, 50Hz
    Cooling Capacity kW 11.2 14 16
    Input W 524 724 940
    Rated current A 2.3 2.85 4.77
    Heating Capacity kW 12.5 16 17
    Input W 524 2.85 940
    Rated current A 2.3 2.7 4.77
    Max. input consumption W 528 724 940
    Max. current A 2.3 2.85 4.77
    Indoor
    fan motor
    Model YSK200-4F-1 YSK300-4C-1 YSK400-4C-2
    Type AC MOTOR
    Brand WELLING YongAn YongAn
    Input W 490 720 930
    Capacitor μF 15 12 15
    Speed (h/m/l) r/min 1000/930/774 860/760/670 1080/920/850
    Indoor coil Number of rows 3 4 4
    Tube pitch(a) ×row
    pitch(b)
    mm 25.4×22 25.4×22 25.4×22
    Fin spacing mm 1.6 1.6 1.6
    Fin type Hydrophilic aluminum
    Tube outside diameter
    and type
    mm Ф9.52
    inner groove tube
    length× height× width mm 700×356×66 996×355.6×88 996×355.6×88
    Number of circuits 7 7 7
    Indoor air flow (H/M/L) m3/h 2116/1936/1520 3000/2618/2226 3620/3044/2744
    *Indoor external static pressure Pa 50(50~ 196) 50(50~ 196) 50(50~ 196)
    Indoor noise level (H/M/L) dB(A) 52/49/47 53/50/48 54/52/50
    Indoor unit Dimension (W×H×D) mm 952×420×690 1300×420×690 1300×420×690
    Packing (W×H×D) mm 1090×440×768 1436×450×768 1436×450×768
    Net/Gross weight kg 50.6/56 68/70 70/77.5
    Refrigerant type R410A
    Throttle Type Electronic expansion valve
    Model BD20FKS, (Winding: DZF20XQ-1000-XHP-6)
    Design pressure(H/L) MPa 4.4/2.6
    Refrigerant piping Liquid / Gas mm Ф9.53/ Ф15.9 Ф9.53/ Ф15.9 Ф9.53/ Ф15.9
    Connecting wiring Power wiring mm2 3×2.5(L20m); 3×3.5(L50m)
    Signal wiring mm2 3×0.75
    Drainage water pipe diameter OD Ф25
    Controller Wired controller KJR-29B1/BK-E (6 meters connection wire)
    Model MDV-D200T1/N1-B(B) MDV-D250T1/N1-B(B) MDV-D280T1/N1-B(B)
    Power supply V- Ph-Hz 220-240V~, 1Ph, 50Hz
    Cooling Capacity kW 20.0 25.0 28.0
    Input W 1516 1516 1516
    Rated current A 8.6 8.6 8.6
    Heating Capacity kW 22.5 26.0 31.5
    Input W 1516 1516 1516
    Rated current A 8.6 8.6 8.6
    Max. input consumption W 1978 1978 1978
    Max. current A 8.6 8.6 8.6
    Indoor fan motor Model YDK550-4X (×2) YDK550-4X (×2) YDK550-4X (×2)
    Type AC Motor
    Brand Man Qi Wei Man Qi Wei Man Qi Wei
    Input W 916/800/675(×2) 916/800/675(×2) 916/800/675(×2)
    Capacitor μF 12(×2) 12(×2) 15(×2)
    Speed (h/m/l) r/min 1200/1065/925(×2) 1200/1065/925(×2) 1200/1065/925(×2)
    Indoor coil Number of rows 4 4 4
    Tube pitch(a) ×row mm 25.4×22 25.4×22 25.4×22
    Fin spacing mm 1.8 1.8 1.8
    Fin type Hydrophilic aluminum
    Tube outside diameter
    and type
    mm Ф9.52
    inner groove tube
    length× height × width mm 1125×508×88 1125×508×88 1125×512×88
    Number of circuits 20 20 20
    Indoor air flow (H/M/L) m3/h 4700/4100/3599 4700/4100/3599 4700/4100/3599
    *Indoor external static pressure Pa 200(50~280) 200(50~280) 200(50~280)
    Indoor noise level (H/M/L) dB(A) 59/55/52 59/55/52 59/55/52
    Indoor unit Dimension (W×H×D) mm 1440×505×925 1440×505×925 1440×505×925
    Packing (W×H×D) mm 1509×550×990 1509×550×990 1509×550×990
    Net/Gross weight kg 115/129 115/129 115/129
    Refrigerant type R410A
    Throttle Type Electronic expansion valve (2 sets throttle boxes each unit)
    Model BD24FKS(L) (Winding: PXR-6-L400-XHP6R/AMP6BL-P)
    Design pressure(H/L) MPa 4.4/2.6
    Refrigerant piping Liquid / Gas mm Ф9.53/ Ф15.9 (×2) Ф9.53/ Ф15.9 (×2) Ф9.53/ Ф15.9 (×2)
    Connecting wiring Power wiring mm2 3×2.5(L20m); 3×3.5(L50m)
    Signal wiring mm2 3×0.75
    Drainage water pipe diameter OD Ф32
    Controller Wired controller KJR-29B1/BK-E (6 meters connection wire)
    Model MDV-D400T1/N1(B) MDV-D450T1/N1(B) MDV-D560T1/N1(B)
    Power supply V- Ph-Hz 220-240V~, 1Ph, 50Hz
    Cooling Capacity kW 40.0 45.0 56.0
    Input W 2700 2700 3400
    Rated current A 12.5 12.5 15.5
    Heating Capacity kW 45 50.0 63.0
    Input W 2700 2700 3400
    Rated current A 12.5 12.5 15.5
    Max. input consumption W 2700 2700 3400
    Max. current A 13.5 13.5 15.5
    Indoor fan motor Model YDK550-4X (×3) YDK550-4X (×3) YDK600-4C (×3)
    Type AC Motor
    Brand Yong An
    Input W 916/800/675(×3) 916/800/675(×3) 1130/990/850(×3)
    Capacitor μF 15(×3) 15(×3) 15(×3)
    Speed (h/m/l) r/min 1200/1065/935(×3) 1200/1065/935(×3) 1280/1135/975(×3)
    Indoor coil Number of rows 5 5 6
    Tube pitch(a) × row mm 21×13.37 21×13.37 21×13.37
    Fin spacing mm 1.5 1.5 1.5
    Fin type Hydrophilic aluminum
    Tube outside diameter
    and type
    mm Ф7
    Inner groove tube
    length× height× width mm 1602×588×67 1602×588×67 1602×588×67
    Number of circuits 28 28 28
    Indoor air flow (H/M/L) m3/h 7472/6072/4995 7472/6072/4995 9550/7950/6600
    *Indoor external static pressure Pa 200(50~280) 200(50~280) 200(50~280)
    Indoor noise level (H/M/L) dB(A) 61/59/56 61/59/56 63/60/57
    Indoor unit Dimension (W×H×D) mm 1970×668×902.5 1970×668×902.5 1970×668×902.5
    Packing (W×H×D) mm 2095×800×964 2095×800×964 2095×800×964
    Net/Gross weight kg 232/245 232/245 235/250
    Refrigerant type R410A
    Throttle Type Electronic expansion valve (4 sets throttle boxes each unit)
    Model BD24FKS(L)
    Design pressure(H/L) MPa 4.4/2.6
    Refrigerant piping Liquid / Gas mm Ф9.53 / Ф22.2(×2) Ф9.53 / Ф22.2(×2) Ф9.53 / Ф22.2(×2)
    Connecting wiring Power wiring mm2 3×2.5(L20m); 3×3.5(L50m)
    Signal wiring mm2 3×0.75
    Drainage water pipe diameter OD Ф32
    Controller Wired controller KJR-29B1/BK-E (6 meters connection wire)
    Notes: 1. Nominal cooling capacities are based on the following conditions: return air temperature : 27°CDB, 19°CWB,
    outdoor air temperature:35°CDB,equivalent ref. Piping: 8m(horizontal).    
    2. Nominal heating capacities are based on the following conditions: return air temperature: 20°CDB,outdoor air temperature:
    7°CDB,6°CWB,equivalent ref. Piping: 8m(horizontal)      
    3. *This is the available static pressure range which means the unit can run stably in this static pressure range, and the optimal
    static pressure range please refers to the Installation Manual. When choosing any static pressure which is out of optimal static
    pressure range, risk like bigger noise, lower air flow volume etc. should be considered in advanced.