Midea "Single-flow indoor units of cassette type Q1DHN1 series"

Suggested retail price

34,030- ... 48,995-hrv.

    Central Controller

    1. The central controller is used for centralized management of indoor units (up to 64 indoor units can be connected via an adapter card).
    2. The indoor units can be divided into 20 zones, each zone can contain no more than 64 indoor units. All indoor units in one zone can only be set to the same mode. (By default, "the zone is not assigned to indoor units").
    3. Users can select the desired mode and temperature with a weekly schedule.

    Dry Mode

    Dry mode automatically selects cooling, based on the difference between fixed and temparaturoy actual room temperature. The temperature is regulated while reducing humidity repeated switching on and off of the cooling and ventilation only. when the dry mode on the remote control shows "Drop"

    Multi-Bend Heat Exchanger

    Increased heat. This unit uses the heat exchangers with tubes of a special design, the inner surface of which has trapezoidal notches "Innergrove cooper", which provides maximum heat transfer surface area increased. Due to this heat increases by 28%, reduced power consumption, and hence increases the efficiency of the system.

    VRF MI2-Q1 series single-flow cassette indoor units are available in 7 models with capacities from 1.8 to 7.1 kW and are equipped with a DC-inverter fan motor.

    Features and benefits of the series:

    •      Ease of installation
    •      Used in rooms with high ceilings (up to 3.2 m)
    •      DC inverter fan motor
    •      7 fan speeds
    •      Uniform air flow
    •      Built-in drain pump
    •      Control panel (optional)
    Model MI2-18Q1DHN1 MI2-22Q1DHN1 MI2-28Q1DHN1 MI2-36Q1DHN1
    Power supply 1-phase, 220-240V, 50/60Hz
    Cooling1 Capacity kW 1.8 2.2 2.8 3.6
    kBtu/h 6.1 7.5 9.6 12.3
    Power input W 25 25 30 30
    Heating2 Capacity kW 2.2 2.6 3.2 4.0
    kBtu/h 7.5 8.9 10.9 13.6
    Power input W 25 25 30 30
    Fan motor Model ZKSP-20-8-1-1
    Type DC
    Brand Panasonic & Welling
    Speed3 r/min 970/910/860/820/780/730/690 1160/1100/1040/1000/960/920/840
    Indoor coil Number of rows 2 2 2 2
    Tube pitch × row pitch mm 21×13.37 21×13.37 21×13.37 21×13.37
    Fin spacing mm 1.5 1.5 1.5 1.5
    Fin type Hydrophilic aluminum
    Tube OD and type mm Ф7 Inner-groove
    Dimensions (L×H×W) mm 760×252.4×26.74
    Number of circuits 2 2 3 3
    Air flow rate3 m3/h 523/482/448/404/360/312/275 573/531/492/456/420/364/315
    Sound pressure level4 dB(A) 37/36/35/34/32/31/30 39/38/37/36/35/35/34
    Main body Net dimensions5 (W×H×D) mm 1054×153×425
    Packed dimensions
    (W×H×D)
    mm 1155×245×490
    Net/Gross weight kg 11.8/15.3 12.3/15.8
    Panel Net dimensions (W×H×D) mm 1180×25×465
    Packed dimensions
    (W×H×D)
    mm 1232×107×517
    Net/Gross weight kg 3.5/5.2
    Refrigerant type R410A R410A R410A R410A
    Throttle Type Electronic expansion valve
    Model D20MISZ-1R(L)
    Design pressure (H/L) MPa 4.4/2.6 4.4/2.6 4.4/2.6 4.4/2.6
    Pipe connections Liquid/Gas pipe mm Ф6.35/Ф12.7
    Drain pipe mm OD Ф32
    Model MI2-45Q1DHN1 MI2-56Q1DHN1 MI2-71Q1DHN1  
    Power supply 1-phase, 220-240V, 50/60Hz  
    Cooling1 Capacity kW 4.5 5.6 7.1  
    kBtu/h 15.4 19.1 24.2  
    Power input W 40 48 60  
    Heating2 Capacity kW 5.0 6.3 8.0  
    kBtu/h 17.1 21.5 27.3  
    Power input W 40 48 60  
    Fan motor Model WZDK60-38G  
    Type DC  
    Brand Welling & Nidec  
    Speed3 r/min 970/950/920/870
    /810/780/760
    1120/1040/1010/980
    /950/920/900
    1150/1120/1080/1040
    /990/930/880
     
    Indoor coil Number of rows 2 2 2  
    Tube pitch × row pitch mm 21×13.37 21×13.37 21×13.37  
    Fin spacing mm 1.5 1.5 1.5  
    Fin type Hydrophilic aluminum  
    Tube OD and type mm Ф7 Inner-groove  
    Dimensions (L×H×W) mm 955×231×26.74  
    Number of circuits 3 3 5  
    Air flow rate3 m3/h 693/662/638/600/556
    /510/476
    792/763/728/688/643
    /589/549
    933/873/815/749/689
    /637/592
     
    Sound pressure level4 dB(A) 41/40/39/38/37/36/35 42/41/40/39/38/37/36 44/43/42/41/39/38/37  
    Main body Net dimensions5
    (W×H×D)
    mm 1275×189×450  
    Packed dimensions
    (W×H×D)
    mm 1370×295×505  
    Net/Gross weight kg 16.1/20.4 16.4/20.7 17.6/22.4  
    Panel Net dimensions
    (W×H×D)
    mm 1350×25×505  
    Packed dimensions
    (W×H×D)
    mm 1410×95×560  
    Net/Gross weight kg 4/5.4  
    Refrigerant type R410A R410A R410A  
    Throttle Type Electronic expansion valve  
    Model D20MISZ-1R(L)  
    Design pressure (H/L) MPa 4.4/2.6 4.4/2.6 4.4/2.6  
    Pipe
    connections
    Liquid/Gas pipe mm Ф6.35/Ф12.7 Ф9.53/Ф15.9  
    Drain pipe mm OD Ф32  
    Notes:            
    1.     Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
    2.     Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
    3.     Fan motor speed and air flow rate are from the highest speed to the lowest speed, total 7 rates for each model.
    4.     Sound pressure level is from highest level to lowest level, total 7 levels for each model. Sound pressure level is measured 1.4m below the unit in a semi-anechoic chamber.
    5.     Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.