Midea "Outdoor monoblocks systems DC Inverter, V6-i series (individual)"

Operating ambient temperatures

Cooling mode
- 5
... + 48 °C
Heating mode
- 25
... + 24 °C

Suggested retail price

305,450- ... 806,675-hrv.

    Blue Fin

    Blue fin heat exchanger cover - Protection against corrosion. Special anti-corrosion coating of the heat exchanger, protection from atmospheric phenomena and effects of aggressive environment. May differ in color (have blue, green, gold or no color at all (clear varnish)

    Compresor DC inverter

    Compressor with inverter DC can increase the efficiency of the air conditioner, thus reducing power consumption saves your costs. This system is much more economical and safer than air conditioners with a constant output of the compressor.

    Multi-Bend Heat Exchanger

    Increased heat. This unit uses the heat exchangers with tubes of a special design, the inner surface of which has trapezoidal notches "Innergrove cooper", which provides maximum heat transfer surface area increased. Due to this heat increases by 28%, reduced power consumption, and hence increases the efficiency of the system.

    Outdoor unit design "Brilliant"

    Designers Midea did not forget about the exterior of the exterior unit of the air conditioner, which in itself is a rarity for climate technology. The outdoor unit is much more elegant than its counterparts, it has facets like a diamond, and attention to detail speaks of a high level of production and a carefully thought-out design concept.

    Sine-Wave Inverter

    Technology 180° -gradusnogo wave inverter conversion - control voltage without the "pulse" effects (jagged sinusoid).

    Compared with the current standard of 120° rectangular wave has the following advantages:

    1. Ability to work with a wider range of supply voltage and frequency.
    2. Most of the energy efficiency and energy conservation.
    3. More soft start, lower noise and vibration.
    4. more control.

    • 13 basic outdoor units with a capacity of 25.2 ~ 90 kW, without the possibility of combining.

    • Modern outdoor units Full DC-Inverter with EVI technology, operation for heating at a temperature of -25°C outside air.

    • Freon cooling of the power control module for compressors.

    • Subcooling by means of an additional plate heat exchanger.

    • All compressors - Hitachiat exchanger.

    • All compressors - Hitachi

    • Advanced microprocessor control.

    • Intelligent defrost cycle during heating operation.

    • Improved oil return program (no oil return loops required).

    • The total capacity of indoor units can be up to 130% of the capacity of the outdoor unit.

    • Can be used in buildings of all sizes, civil engineering and commercial real estate.

    • Automatic addressing of indoor units.

    • From 2021, they will be equipped with a Black Box board for accumulating diagnostic data.

    HP     8 10 12 14
    Model name     MV6-i252WV2GN1-E MV6-i280WV2GN1-E MV6-i335WV2GN1-E MV6-i400WV2GN1-E
    Power supply   V/Ph/Hz 380-415/3/50
    Cooling1 Capacity kW 25.2 28.0 33.5 40.0
        kBtu/h 86.0 95.5 114.3 136.5
      Power input kW 5.5 6.7 8.9 11.0
      EER   4.55 4.20 3.75 3.65
    Heating2 Capacity kW 25.2 28.0 33.5 40.0
        kBtu/h 86.0 95.5 114.3 136.5
      Power input kW 4.8 5.5 7.6 9.3
      COP   5.20 5.10 4.40 4.30
    Connected
    indoor unit
    Total capacity   50-130% of outdoor unit capacity
      Maximum quantity   13 16 20 23
    Compressor Type   DC inverter
      Quantity   1
      Oil type   FV68H
      Start-up method   Soft start
    Fan Type   Propeller
      Motor type   DC
      Quantity   1
      Motor output kW 0.56 0.56 0.56 0.92
      Airflow rate m3/h 11000 11000 11000 13000
      Drive type   Direct
    Refrigerant Type   R410A
      Factory charge kg 11 11 11 13
    Pipe
    connections3
    Liquid pipe mm Φ12.7 Φ15.9 Φ15.9
      Gas pipe mm Φ25.4 Φ28.6 Φ31.8
    Sound pressure level4   dB(A) 58 60 62
    Sound power level   dB(A) 78 81 85
    Net dimensions (W×H×D)   mm 990×1635×790 1340×1635×850
    Packed dimensions (W×H×D)   mm 1090×1805×860 1405×1805×910
    Net weight   kg 227 277
    Gross weight   kg 242 304
    Ambient temp. operation
    range
    Cooling oC -5 ~ 48
      Heating oC -25 ~ 24
    Notes:
    1.     Indoor air temperature 27°C DB, 19°C WB; outdoor air temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
    2.     Indoor air temperature 20°C DB; outdoor air temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
    3.     Diameters given are those of the unit's stop valve.
    4.     Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.
    HP     16 18 20 22
    Model name     MV6-i450WV2GN1-E MV6-i500WV2GN1-E MV6-i560WV2GN1-E MV6-i615WV2GN1-E
    Power supply   V/Ph/Hz 380-415/3/50
    Cooling1 Capacity kW 45.0 50.0 56.0 61.5
        kBtu/h 153.5 170.6 191.1 209.8
      Power input kW 12.9 14.7 16.0 20.2
      EER   3.50 3.40 3.50 3.05
    Heating2 Capacity kW 45.0 50.0 56.0 61.5
        kBtu/h 153.5 170.6 191.1 209.8
      Power input kW 10.7 12.2 13.8 17.6
      COP   4.20 4.10 4.05 3.50
    Connected
    indoor unit
    Total capacity   50-130% of outdoor unit capacity
      Maximum quantity   26 29 33 36
    Compressor Type   DC inverter
      Quantity   1 2
      Oil type   FV68H
      Start-up method   Soft start
    Fan Type   Propeller
      Motor type   DC
      Quantity   1 2
      Motor output kW 0.92 0.92 0.56×2 0.56×2
      Airflow rate m3/h 13000 13000 17000 17000
      Drive type   Direct
    Refrigerant Type   R410A
      Factory charge kg 13 13 17 17
    Pipe
    connections3
    Liquid pipe mm Φ15.9 Φ19.1
      Gas pipe mm Φ31.8 Φ31.8
    Sound pressure level4   dB(A) 65 66
    Sound power level   dB(A) 88
    Net dimensions (W×H×D)   mm 1340×1635×850 1340×1635×825
    Packed dimensions (W×H×D)   mm 1405×1805×910
    Net weight   kg 277 295 344 344
    Gross weight   kg 304 322 364 364
    Ambient temp. operation
    range
    Cooling oC -5 ~ 48
      Heating oC -25 ~ 24
    Notes:
    1.     Indoor air temperature 27°C DB, 19°C WB; outdoor air temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
    2.     Indoor air temperature 20°C DB; outdoor air temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
    3.     Diameters given are those of the unit's stop valve.
    4.     Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.
    HP     24 26 28 30
    Model name     MV6-i670WV2GN1-E MV6-i730WV2GN1-E MV6-i785WV2GN1-E MV6-i850WV2GN1-E
    Power supply   V/Ph/Hz 380-415/3/50      
    Cooling1 Capacity kW 67.0 73.0 78.5 85.0
        kBtu/h 228.6 249.1 267.8 290.0
      Power input kW 21.6 21.6 24.9 28.3
      EER   3.10 3.40 3.15 3.00
    Heating2 Capacity kW 67.0 73.0 78.5 85.0
        kBtu/h 228.6 249.1 267.8 290.0
      Power input kW 16.8 18.1 21.8 24.3
      COP   4.00 4.05 3.60 3.50
    Connected
    indoor unit
    Total capacity   50-130% of outdoor unit capacity
      Maximum quantity   39 43 46 50
    Compressor Type   DC inverter
      Quantity   2
      Oil type   FV68H
      Start-up method   Soft start
    Fan Type   Propeller
      Motor type   DC
      Quantity   2
      Motor output kW 0.92×2 0.92×2 0.92×2 0.92×2
      Airflow rate m3/h 25000 25000 25000 24000
      Drive type   Direct
    Refrigerant Type   R410A
      Factory charge kg 22 22 22 25
    Pipe
    connections3
    Liquid pipe mm Φ19.1 Φ22.2 Φ22.2
      Gas pipe mm Φ31.8 Φ31.8 Φ38.1
    Sound pressure level4   dB(A) 67 68
    Sound power level   dB(A) 89 90
    Net dimensions (W×H×D)   mm 1730×1830×850
    Packed dimensions (W×H×D)   mm 1800×2000×910
    Net weight   kg 407 429 475
    Gross weight   kg 430 452 507
    Ambient temp. operation
    range
    Cooling oC -5 ~ 48
      Heating oC -25 ~ 24
    Notes:
    1.     Indoor air temperature 27°C DB, 19°C WB; outdoor air temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
    2.     Indoor air temperature 20°C DB; outdoor air temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
    3.     Diameters given are those of the unit's stop valve.
    4.     Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.