Midea "Indoor MDV units of channel type MI2, high pressure, T1DHN1 series"

Suggested retail price

48,175- ... 192,290-hrv.

    Central Controller

    1. The central controller is used for centralized management of indoor units (up to 64 indoor units can be connected via an adapter card).
    2. The indoor units can be divided into 20 zones, each zone can contain no more than 64 indoor units. All indoor units in one zone can only be set to the same mode. (By default, "the zone is not assigned to indoor units").
    3. Users can select the desired mode and temperature with a weekly schedule.

    Multi-Bend Heat Exchanger

    Increased heat. This unit uses the heat exchangers with tubes of a special design, the inner surface of which has trapezoidal notches "Innergrove cooper", which provides maximum heat transfer surface area increased. Due to this heat increases by 28%, reduced power consumption, and hence increases the efficiency of the system.

    The high-pressure indoor units of the MI2-T1DHN1 series are presented in a wide range of high-power models designed for servicing commercial and industrial premises. External static pressure up to 200 Pa (models 71-140), 250 Pa (models 160-280), 400 Pa (models 400-560).

    Features and benefits:

    • DC fan motor
    • 7 fan speeds
    • The standard filter is mounted in an aluminum frame, which is removed by moving down from the bottom of the case
    • There is a fence of fresh air and flanges for easy connection of air ducts
    • The maximum length of air supply is about 14 m.
    • The maximum height of air supply is about 6.5 m.
    • Remote control (option)
    Model name MI2-71T1DHN1 MI2-80T1DHN1 MI2-90T1DHN1
    Power supply 1-phase, 220-240V, 50/60Hz
    Cooling1 Capacity kW 7.1 8 9
    kBut/h 24.2 27.3 30.7
    Input W 180 180 220
    Heating2 Capacity kW 8 9 10
    kBut/h 27.3 30.7 34.1
    Input W 180 180 220
    Fan motor Model WZDK750-38G-W WZDK750-38G-W WZDK750-38G-W
    Type DC
    Brand Pansonic/ Welling
    Speed (H/M/L) r/min 970/950/940/910/880/860/840 980/950/930/900/870/840/810
    Coil Number of rows 2 2 3
    Tube  pitch  ×  row mm 25.4×22 25.4×22 25.4×22
    Fin spacing mm 1.5 1.5 1.6
    Fin type Hydrophilic aluminum
    Tube OD and type mm Ф9.53 Inner groove
    Dimensions (L×H ×W) mm 700×356×44 700×356×44 700×356×66
    Number of circuits 3 3 7
    Airflow rate3 m3/h 1360/1327/1293/1260/1227/1193/1160 1420/1373/1327/1280/1233/1187/1140
    External static pressure4 Pa 100 (30~ 200)
    Sound pressure level5 dB(A) 46/46/45/45/44/43/42 46/46/45/45/44/43/42 50/49/48/48/47/46/45
    Unit Net dimensions6 (W×H×D) mm 952×420×690
    Packed dimensions
    (W×H×D)
    mm 1090×440×768
    Net/Gross weight kg 41/47 41/47 51/57
    Refrigerant type R410A
    Throttle Type Electronic expansion valve
    Model BD20FKS(L)
    Design pressure (H/L) MPa 4.4/2.6
    Pipe
    connections
    Liquid/Gas pipe mm Ф9.53/Ф15.9
    Drain pipe mm OD Ф25
    Model name MI2-112T1DHN1 MI2-140T1DHN1 MI2-160T1DHN1
    Power supply 1-phase, 220-240V, 50/60Hz
    Cooling1 Capacity kW 11.2 14 16
    kBut/h 38.2 47.8 54.6
    Input W 380 420 700
    Heating2 Capacity kW 12.5 16 17
    kBut/h 42.7 54.6 58
    Input W 380 420 700
    Fan motor Model WZDK750-38G-W WZDK750-38GS-W WZDK750-38GS-W
    Type DC
    Brand Pansonic/ Welling
    Speed (H/M/L) r/min 1110/1070/1010/970/920/870/840 1015/975/935/905/845/805/765 1080/1050/1000/960/920/870/830
    Coil Number of rows 3 4 4
    Tube pitch × row pitch mm 25.4×22 25.4×22 25.4×22
    Fin spacing mm 1.6 1.6 1.6
    Fin type Hydrophilic aluminum
    Tube OD and type mm Ф9.53 Inner groove
    Dimensions (L×H ×W) mm 700×356×66 996×356×88 996×356×88
    Number of circuits 7 7 7
    Airflow rate3 m3/h 1870/1783/1697/1610/1523/1437/1350 2240/2133/2027/1920/1813/1707/1600 2660/2530/2400/2270/2140/2010/1880
    External static pressure4 Pa 100 (30~ 200)
    Sound pressure level5 dB(A) 50/50/49/48/47/46/45 53/52/51/51/50/49/48 54/54/53/52/51/50/50
    Unit Net dimensions6 (W×H×D) mm 952×420×690 1300×420×690 1300×420×690
    Packed dimensions
    (W×H×D)
    mm 1090×440×768 1436×450×768 1436×450×768
    Net/Gross weight kg 51/57 63/70 63/70
    Refrigerant type R410A
    Throttle Type Electronic expansion valve
    Model BD20FKS(L)
    Design pressure (H/L) MPa 4.4/2.6
    Pipe
    connections
    Liquid/Gas pipe mm Ф9.53/Ф19.1
    Drain pipe mm OD Ф25
    Model name MI2-200T1DHN1 MI2-250T1DHN1 MI2-280T1DHN1
    Power supply 1-phase, 220-240V, 50/60Hz
    Cooling1 Capacity kW 20 25 28
    kBut/h 68.2 85.3 95.5
    Input W 990 990 1200
    Heating2 Capacity kW 22.5 26 31.5
    kBut/h 76.8 88.7 107.5
    Input W 990 990 1200
    Fan motor Model ZKSN-920-8-12 ZKSN-920-8-12 ZKSN-920-8-12
    Type DC
    Brand Nidec/Yongan
    Speed (H/M/L) r/min 1210/1180/1150/1130/1100/1080/1050
    Coil Number of rows 4 4 4
    Tube pitch × row pitch mm 25.4×22 25.4×22 25.4×22
    Fin spacing mm 1.8 1.8 1.8
    Fin type Hydrophilic aluminum
    Tube OD and type mm Ф9.53 Inner groove
    Dimensions (L×H ×W) mm 1125×512×88 1125×512×88 1125×512×88
    Number of circuits 20 20 20
    Airflow rate3 m3/h 4330/4230/4130/4030/3930/3830/3730
    External static pressure4 Pa 170 (20~250)
    Sound pressure level5 dB(A) 57/56/55/54/53/52/50
    Unit Net dimensions6 (W×H×D) mm 1440×505×925
    Packed dimensions
    (W×H×D)
    mm 1509×550×990
    Net/Gross weight kg 130/142
    Refrigerant type R410A
    Throttle Type Electronic expansion valve
    Model D20MISZ-1R(L)
    Design pressure (H/L) MPa 4.4/2.6
    Pipe
    connections
    Liquid/Gas pipe mm Ф12.7/Ф22.2
    Drain pipe mm OD Ф32
    Notes:
    1.     Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
    2.     Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
    3.     Fan motor speed and air flow rate are from the highest speed to the lowest speed, total 7 rates for each model.
    4.     Stable operation external static pressure range. (Note: setting external static pressure outside the unit ’s optimal static pressure range
     may lead to higher noise levels and lower airflow rate. For the optimal external static pressure range refer to the unit’s installation manual.)
    5.    Sound pressure level is from highest level to lowest level, total 7 levels for each model. Sound pressure level is measured 1.4m below the unit in a
    semi-anechoic chamber.
    6.     Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.