Suggested retail price
Technology
Aluminium heat exchanger with hydrophilic coating
Improved wettability of the heat exchanger aluminum plates which have a special coating with a hydrophilic layer, ensuring rapid removal of condensate from the indoor unit that does not allow to quickly form of mold and bacteria, providing a more efficient operation of the air conditioner.
Central Controller
- The central controller is used for centralized management of indoor units (up to 64 indoor units can be connected via an adapter card).
- The indoor units can be divided into 20 zones, each zone can contain no more than 64 indoor units. All indoor units in one zone can only be set to the same mode. (By default, "the zone is not assigned to indoor units").
- Users can select the desired mode and temperature with a weekly schedule.
360°Air Flow Panel
With the 360°air flow panel, the air can be distributed to every corner of the room.
Night Mode
Mode is activated with the remote control and provides a comfortable environment for a peaceful and deep sleep during the 7-hour cycle with a temperature change of reference values, as well as setting the minimum noise level and economical energy consumption. After that, the temperature returns to the originally specified value.
The mixing of fresh air
Organization of fresh air - by a separate duct (in a split system with such a function, the duct is usually a small diameter and is laid along the highway) ...
Redirecting the flow of air to neighboring rooms using air ducts
With the help of air ducts, it is possible to organize the redirection of part of the treated air flow to neighboring rooms.
Dry Mode
Dry mode automatically selects cooling, based on the difference between fixed and temparaturoy actual room temperature. The temperature is regulated while reducing humidity repeated switching on and off of the cooling and ventilation only. when the dry mode on the remote control shows "Drop"
Temperature compensation
The function of temperature compensation corrects the temperature in the person's zone of being comfortable, (because the air temperature near the floor and ceiling can differ by several degrees) by further increasing / decreasing the temperature from the value set from the remote control. Thus, compensation and equalization of the overall room temperature occurs. For household split systems, the value is set by the manufacturer and is 2°C.
Multi-Bend Heat Exchanger
Increased heat. This unit uses the heat exchangers with tubes of a special design, the inner surface of which has trapezoidal notches "Innergrove cooper", which provides maximum heat transfer surface area increased. Due to this heat increases by 28%, reduced power consumption, and hence increases the efficiency of the system.
Description
- The block design is similar to the MCC cassette semi-industrial blocks;
- Built-in drainage pump with a lift height of up to 750 mm;
- Easy installation and maintenance;
- A hole in the corner of the unit body for organizing the supply of fresh air;
4 fan speeds; - LED-display on the T-MBQ4-02C1 (B1) panel, for monitoring and displaying the operating modes of the system;
- 2 stepper motors to control blinds with an opening angle of 38-42 degrees;
- Low noise level;
- Infrared remote control (IR) remote control;
Specifications
Model | MDV-D28Q4/N1-E | MDV-D36Q4/N1-E | MDV-D45Q4/N1-E | ||
Power supply | 220-240V~ 50Hz | ||||
Cooling | Capacity | kW | 2.8 | 3.6 | 4.5 |
Power input | W | 80 | 80 | 88 | |
Heating | Capacity | kW | 3.2 | 4 | 5 |
Power input | W | 80 | 80 | 88 | |
Indoor fan motor | Model | YDK26-6S | |||
Type | AC motor | ||||
Brand | Weiling, Tongde, Dayang | ||||
Insulation class | B | ||||
Safe class | IP20 | ||||
Input | W | 70 | 70 | 80 | |
Output | W | 26 | 26 | 26 | |
Capacitor | uF | 2 | 2 | 3 | |
Indoor fan | Material | Plastic | |||
Type | Centrifugal fan | ||||
Diameter | mm | 476 | |||
Height | mm | 125 | |||
Indoor coil | Number of rows | 1 | 1 | 2 | |
Tube pitch(a)×row pitch(b) | mm | 21×13.37 | |||
Fin spacing | mm | 1.5 | |||
Fin type | Hydrophilic aluminium | ||||
Tube size | mm | Ф7 | |||
Tube type | Innergroove tube | ||||
Coil length×height | mm | 2033×168 | 2051×168 | ||
Number of circuits | 4 | 8 | |||
Indoor air flow (H/M/L) | m3/h | 764/638//554 | 764/638//554 | 905/740//651 | |
Sound pressure level (H/M/L) | dB(A) | 32/31/30 | 32/31/30 | 36/34/33 | |
Indoor unit body | Net dimension (W×H×D) | mm | 840×230×840 | ||
Packing size (W×H×D) | mm | 955×260×955 | |||
Net/Gross weight | kg | 21.5/26.7 | 21.5/26.7 | 23.7/28.9 | |
Indoor unit panel | Model | T-MBQ4-02B1 | |||
Net dimension (W×H×D) | mm | 950×54.5×950 | |||
Packing size (W×H×D) | mm | 1035×90×1035 | |||
Net/Gross weight | kg | 6/9 | |||
Refrigerant type | R410A | ||||
Throttle type | Electronic expansion valve | ||||
Design pressure (H/L) | MPa | 4.4/2.6 | |||
Pipe connections | Liquid pipe | mm | Φ6.35 | ||
Gas pipe | mm | Φ12.7 | |||
Drain pipe | mm | Φ32 | |||
Controller | Wireless remote controller | ||||
Notes: | |||||
Capacities are based on the following conditions: | |||||
Cooling: Indoor temperature 27°C DB / 19°C WB; Outdoor temperature 35°C DB / 24°C WB. Heating: Indoor temperature 20°C DB / 15°C WB; Outdoor temperature 7°C DB / 6°C WB. Piping length: Interconnecting piping length is 7.5m, level difference is 0m. | |||||
Sound values are measured in a semi-anechoic room, at a position 1.4m downward from the unit center |
Model | MDV-D56Q4/N1-E | MDV-D71Q4/N1-E | MDV-D80Q4/N1-E | ||
Power supply | 220-240V~ 50Hz | ||||
Cooling | Capacity | kW | 5.6 | 7.1 | 8 |
Power input | W | 88 | 88 | 110 | |
Heating | Capacity | kW | 6.3 | 8 | 9 |
Power input | W | 88 | 88 | 110 | |
Indoor fan motor | Model | YDK26-6S | YDK30-6S | YDK37-6S | |
Type | AC motor | ||||
Brand | Weiling, Tongde, Dayang | ||||
Insulation class | B | ||||
Safe class | IP20 | ||||
Input | W | 80 | 80 | 100 | |
Output | W | 26 | 30 | 37 | |
Capacitor | uF | 3 | 2.5 | 3.5 | |
Indoor fan | Material | Plastic | |||
Type | Centrifugal fan | ||||
Diameter | mm | 476 | |||
Height | mm | 125 | |||
Indoor coil | Number of rows | 2 | 2 | 2 | |
Tube pitch(a)×row pitch(b) | mm | 21×13.37 | |||
Fin spacing | mm | 1.5 | |||
Fin type | Hydrophilic aluminium | ||||
Tube size | mm | Ф7 | |||
Tube type | Innergroove tube | ||||
Coil length×height | mm | 2051×168 | |||
Number of circuits | 8 | 8 | 8 | ||
Indoor air flow (H/M/L) | m3/h | 905/740//651 | 950/767//663 | 1200/1021/789 | |
Sound pressure level (H/M/L) | dB(A) | 36/34/33 | 38/36/35 | 42/39/37 | |
Indoor unit body | Net dimension (W×H×D) | mm | 840×230×840 | ||
Packing size (W×H×D) | mm | 955×260×955 | |||
Net/Gross weight | kg | 23.7/28.9 | |||
Indoor unit panel | Model | T-MBQ4-02B1 | |||
Net dimension (W×H×D) | mm | 950×54.5×950 | |||
Packing size (W×H×D) | mm | 1035×90×1035 | |||
Net/Gross weight | kg | 6/9 | |||
Refrigerant type | R410A | ||||
Throttle type | Electronic expansion valve | ||||
Design pressure (H/L) | MPa | 4.4/2.6 | |||
Pipe connections | Liquid pipe | mm | Φ9.53 | ||
Gas pipe | mm | Φ15.9 | |||
Drain pipe | mm | Φ32 | |||
Controller | Wireless remote controller | ||||
Notes: | |||||
Capacities are based on the following conditions: | |||||
Cooling: Indoor temperature 27°C DB / 19°C WB; Outdoor temperature 35°C DB / 24°C WB. Heating: Indoor temperature 20°C DB / 15°C WB; Outdoor temperature 7°C DB / 6°C WB. Piping length: Interconnecting piping length is 7.5m, level difference is 0m. | |||||
Sound values are measured in a semi-anechoic room, at a position 1.4m downward from the unit center |
Model | MDV-D90Q4/N1-E | MDV-D100Q4/N1-E | MDV-D112Q4/N1-E | MDV-D140Q4/N1-E | ||
Power supply | 220-240V~ 50Hz | |||||
Cooling | Capacity | kW | 9 | 10 | 11.2 | 14 |
Power input | W | 140 | 165 | 165 | 176 | |
Heating | Capacity | kW | 10 | 11.1 | 12.5 | 16 |
Power input | W | 140 | 165 | 165 | 176 | |
Indoor fan motor | Model | YDK50-6S | YDK65-6S | YDK65-6S | YDK65-6S | |
Type | AC motor | |||||
Brand | Weiling, Tongde, Dayang | |||||
Insulation class | B | |||||
Safe class | IP20 | |||||
Input | W | 130 | 150 | 150 | 160 | |
Output | W | 50 | 65 | 65 | 65 | |
Capacitor | uF | 2.5 | 3.5 | 3.5 | 4 | |
Indoor fan | Material | Plastic | ||||
Type | Centrifugal fan | |||||
Diameter | mm | 476 | ||||
Height | mm | 170 | ||||
Indoor coil | Number of rows | 2 | 2 | 2 | 3 | |
Tube pitch(a)× row pitch(b) |
mm | 21×13.37 | ||||
Fin spacing | mm | 1.5 | ||||
Fin type | Hydrophilic aluminium | |||||
Tube size | mm | Ф7 | ||||
Tube type | Innergroove tube | |||||
Coil length×height | mm | 2051×252 | 2007×252 | |||
Number of circuits | 8 | 8 | 8 | 12 | ||
Indoor air flow (H/M/L) | m3/h | 1332/1129/908 | 1651/1304/1127 | 1651/1304/1127 | 1658/1335/1130 | |
Sound pressure level (H/M/L) | dB(A) | 43/39/38 | 45/42/40 | 45/42/40 | 46/41/39 | |
Indoor unit body | Net dimension (W×H×D) |
mm | 840×300×840 | |||
Packing size (W×H×D) |
mm | 955×330×955 | ||||
Net/Gross weight | kg | 28.7/34.1 | 28.7/34.1 | 28.7/34.1 | 30.9/36.3 | |
Indoor unit panel | Model | T-MBQ4-02B1 | ||||
Net dimension (W×H×D) |
mm | 950×54.5×950 | ||||
Packing size (W×H×D) |
mm | 1035×90×1035 | ||||
Net/Gross weight | kg | 6/9 | ||||
Refrigerant type | R410A | |||||
Throttle type | Electronic expansion valve | |||||
Design pressure (H/L) | MPa | 4.4/2.6 | ||||
Pipe connections | Liquid pipe | mm | Φ9.53 | |||
Gas pipe | mm | Φ15.9 | ||||
Drain pipe | mm | Φ32 | ||||
Controller | Wireless remote controller | |||||
Notes: | ||||||
Capacities are based on the following conditions: | ||||||
Cooling: Indoor temperature 27°C DB / 19°C WB; Outdoor temperature 35°C DB / 24°C WB. Heating: Indoor temperature 20°C DB / 15°C WB; Outdoor temperature 7°C DB / 6°C WB. Piping length: Interconnecting piping length is 7.5m, level difference is 0m. | ||||||
Sound values are measured in a semi-anechoic room, at a position 1.4m downward from the unit center |