Midea "Indoor unit cassette type 4-way, Standart series Q4/N1-E(B)"

Suggested retail price

34,235- ... 48,585-hrv.

    Central Controller

    1. The central controller is used for centralized management of indoor units (up to 64 indoor units can be connected via an adapter card).
    2. The indoor units can be divided into 20 zones, each zone can contain no more than 64 indoor units. All indoor units in one zone can only be set to the same mode. (By default, "the zone is not assigned to indoor units").
    3. Users can select the desired mode and temperature with a weekly schedule.

    Night Mode

    Mode is activated with the remote control and provides a comfortable environment for a peaceful and deep sleep during the 7-hour cycle with a temperature change of reference values​​, as well as setting the minimum noise level and economical energy consumption. After that, the temperature returns to the originally specified value.

    Dry Mode

    Dry mode automatically selects cooling, based on the difference between fixed and temparaturoy actual room temperature. The temperature is regulated while reducing humidity repeated switching on and off of the cooling and ventilation only. when the dry mode on the remote control shows "Drop"

    Temperature compensation

    The function of temperature compensation corrects the temperature in the person's zone of being comfortable, (because the air temperature near the floor and ceiling can differ by several degrees) by further increasing / decreasing the temperature from the value set from the remote control. Thus, compensation and equalization of the overall room temperature occurs. For household split systems, the value is set by the manufacturer and is 2°C.

    Multi-Bend Heat Exchanger

    Increased heat. This unit uses the heat exchangers with tubes of a special design, the inner surface of which has trapezoidal notches "Innergrove cooper", which provides maximum heat transfer surface area increased. Due to this heat increases by 28%, reduced power consumption, and hence increases the efficiency of the system.

    • The block design is similar to the MCC cassette semi-industrial blocks;
    • Built-in drainage pump with a lift height of up to 750 mm;
    • Easy installation and maintenance;
    • A hole in the corner of the unit body for organizing the supply of fresh air;
      4 fan speeds;
    • LED-display on the T-MBQ4-02C1 (B1) panel, for monitoring and displaying the operating modes of the system;
    • 2 stepper motors to control blinds with an opening angle of 38-42 degrees;
    • Low noise level;
    • Infrared remote control (IR) remote control;
    Model MDV-D28Q4/N1-E MDV-D36Q4/N1-E MDV-D45Q4/N1-E
    Power supply 220-240V~ 50Hz
    Cooling Capacity kW 2.8 3.6 4.5
    Power input W 80 80 88
    Heating Capacity kW 3.2 4 5
    Power input W 80 80 88
    Indoor fan motor Model YDK26-6S
    Type AC motor
    Brand Weiling, Tongde, Dayang
    Insulation class B
    Safe class IP20
    Input W 70 70 80
    Output W 26 26 26
    Capacitor uF 2 2 3
    Indoor fan Material Plastic
    Type Centrifugal fan
    Diameter mm 476
    Height mm 125
    Indoor coil Number of rows 1 1 2
    Tube pitch(a)×row pitch(b) mm 21×13.37
    Fin spacing mm 1.5
    Fin type Hydrophilic aluminium
    Tube size mm Ф7
    Tube type Innergroove tube
    Coil length×height mm 2033×168 2051×168
    Number of circuits 4 8
    Indoor air flow (H/M/L) m3/h 764/638//554 764/638//554 905/740//651
    Sound pressure level (H/M/L) dB(A) 32/31/30 32/31/30 36/34/33
    Indoor unit body Net dimension (W×H×D) mm 840×230×840
    Packing size (W×H×D) mm 955×260×955
    Net/Gross weight kg 21.5/26.7 21.5/26.7 23.7/28.9
    Indoor unit panel Model T-MBQ4-02B1
    Net dimension (W×H×D) mm 950×54.5×950
    Packing size (W×H×D) mm 1035×90×1035
    Net/Gross weight kg 6/9
    Refrigerant type R410A
    Throttle type Electronic expansion valve
    Design pressure (H/L) MPa 4.4/2.6
    Pipe connections Liquid pipe mm Φ6.35
    Gas pipe mm Φ12.7
    Drain pipe mm Φ32
    Controller Wireless remote controller
    Notes:
    Capacities are based on the following conditions:
    Cooling: Indoor temperature 27°C DB / 19°C WB; Outdoor temperature 35°C DB / 24°C WB. Heating: Indoor temperature 20°C DB / 15°C WB; Outdoor temperature 7°C DB / 6°C WB. Piping length: Interconnecting piping length is 7.5m, level difference is 0m.
    Sound values are measured in a semi-anechoic room, at a position 1.4m downward from the unit center
    Model MDV-D56Q4/N1-E MDV-D71Q4/N1-E MDV-D80Q4/N1-E
    Power supply 220-240V~ 50Hz
    Cooling Capacity kW 5.6 7.1 8
    Power input W 88 88 110
    Heating Capacity kW 6.3 8 9
    Power input W 88 88 110
    Indoor fan motor Model YDK26-6S YDK30-6S YDK37-6S
    Type AC motor
    Brand Weiling, Tongde, Dayang
    Insulation class B
    Safe class IP20
    Input W 80 80 100
    Output W 26 30 37
    Capacitor uF 3 2.5 3.5
    Indoor fan Material Plastic
    Type Centrifugal fan
    Diameter mm 476
    Height mm 125
    Indoor coil Number of rows 2 2 2
    Tube pitch(a)×row pitch(b) mm 21×13.37
    Fin spacing mm 1.5
    Fin type Hydrophilic aluminium
    Tube size mm Ф7
    Tube type Innergroove tube
    Coil length×height mm 2051×168
    Number of circuits 8 8 8
    Indoor air flow (H/M/L) m3/h 905/740//651 950/767//663 1200/1021/789
    Sound pressure level (H/M/L) dB(A) 36/34/33 38/36/35 42/39/37
    Indoor unit body Net dimension (W×H×D) mm 840×230×840
    Packing size (W×H×D) mm 955×260×955
    Net/Gross weight kg 23.7/28.9
    Indoor unit panel Model T-MBQ4-02B1
    Net dimension (W×H×D) mm 950×54.5×950
    Packing size (W×H×D) mm 1035×90×1035
    Net/Gross weight kg 6/9
    Refrigerant type R410A
    Throttle type Electronic expansion valve
    Design pressure (H/L) MPa 4.4/2.6
    Pipe connections Liquid pipe mm Φ9.53
    Gas pipe mm Φ15.9
    Drain pipe mm Φ32
    Controller Wireless remote controller
    Notes:
    Capacities are based on the following conditions:
    Cooling: Indoor temperature 27°C DB / 19°C WB; Outdoor temperature 35°C DB / 24°C WB. Heating: Indoor temperature 20°C DB / 15°C WB; Outdoor temperature 7°C DB / 6°C WB. Piping length: Interconnecting piping length is 7.5m, level difference is 0m.
    Sound values are measured in a semi-anechoic room, at a position 1.4m downward from the unit center
    Model MDV-D90Q4/N1-E MDV-D100Q4/N1-E MDV-D112Q4/N1-E MDV-D140Q4/N1-E
    Power supply 220-240V~ 50Hz
    Cooling Capacity kW 9 10 11.2 14
    Power input W 140 165 165 176
    Heating Capacity kW 10 11.1 12.5 16
    Power input W 140 165 165 176
    Indoor fan motor Model YDK50-6S YDK65-6S YDK65-6S YDK65-6S
    Type AC motor
    Brand Weiling, Tongde, Dayang
    Insulation class B
    Safe class IP20
    Input W 130 150 150 160
    Output W 50 65 65 65
    Capacitor uF 2.5 3.5 3.5 4
    Indoor fan Material Plastic
    Type Centrifugal fan
    Diameter mm 476
    Height mm 170
    Indoor coil Number of rows 2 2 2 3
    Tube pitch(a)×
    row pitch(b)
    mm 21×13.37
    Fin spacing mm 1.5
    Fin type Hydrophilic aluminium
    Tube size mm Ф7
    Tube type Innergroove tube
    Coil length×height mm 2051×252 2007×252
    Number of circuits 8 8 8 12
    Indoor air flow (H/M/L) m3/h 1332/1129/908 1651/1304/1127 1651/1304/1127 1658/1335/1130
    Sound pressure level (H/M/L) dB(A) 43/39/38 45/42/40 45/42/40 46/41/39
    Indoor unit body Net dimension
    (W×H×D)
    mm 840×300×840
    Packing size
    (W×H×D)
    mm 955×330×955
    Net/Gross weight kg 28.7/34.1 28.7/34.1 28.7/34.1 30.9/36.3
    Indoor unit panel Model T-MBQ4-02B1
    Net dimension
    (W×H×D)
    mm 950×54.5×950
    Packing size
    (W×H×D)
    mm 1035×90×1035
    Net/Gross weight kg 6/9
    Refrigerant type R410A
    Throttle type Electronic expansion valve
    Design pressure (H/L) MPa 4.4/2.6
    Pipe connections Liquid pipe mm Φ9.53
    Gas pipe mm Φ15.9
    Drain pipe mm Φ32
    Controller Wireless remote controller
    Notes:  
    Capacities are based on the following conditions:  
    Cooling: Indoor temperature 27°C DB / 19°C WB; Outdoor temperature 35°C DB / 24°C WB. Heating: Indoor temperature 20°C DB / 15°C WB; Outdoor temperature 7°C DB / 6°C WB. Piping length: Interconnecting piping length is 7.5m, level difference is 0m.  
    Sound values are measured in a semi-anechoic room, at a position 1.4m downward from the unit center