Operating ambient temperatures
Suggested retail price
Technology
Blue Fin
Blue fin heat exchanger cover - Protection against corrosion. Special anti-corrosion coating of the heat exchanger, protection from atmospheric phenomena and effects of aggressive environment. May differ in color (have blue, green, gold or no color at all (clear varnish)
Compresor DC inverter
Compressor with inverter DC can increase the efficiency of the air conditioner, thus reducing power consumption saves your costs. This system is much more economical and safer than air conditioners with a constant output of the compressor.
DC inverter motor Outdoor Unit
In outdoor units, a DC motor is used to rotate the fan. This allows you to significantly reduce noise and power consumption. And also get several positions of the fan speed, depending on the needs of the system.
Multi-Bend Heat Exchanger
Increased heat. This unit uses the heat exchangers with tubes of a special design, the inner surface of which has trapezoidal notches "Innergrove cooper", which provides maximum heat transfer surface area increased. Due to this heat increases by 28%, reduced power consumption, and hence increases the efficiency of the system.
Sine-Wave Inverter
Technology 180° -gradusnogo wave inverter conversion - control voltage without the "pulse" effects (jagged sinusoid).
Compared with the current standard of 120° rectangular wave has the following advantages:
- Ability to work with a wider range of supply voltage and frequency.
- Most of the energy efficiency and energy conservation.
- More soft start, lower noise and vibration.
- more control.
Description
- The model range is represented by outdoor units with a capacity of 12-18 kW;
- Double rotor DC-Inverter compressor with high efficiency and low noise and vibration;
- DC-Inverter fan motors, the efficiency of which is 30% higher than that of “conventional” (AC) fans, fans and protective grilles are modified to reduce noise;
- Heat exchangers with a protective coating "Blue fin" are used, which have increased corrosion resistance;
- 2 options for organizing the trunk to indoor units are allowed - branching by means of rinets or using special refrigerant switching units (Branch-providers FTQ4-01). Branch providers are supplied in 4-port only and in max. a 16 kW system can use no more than two providers installed in parallel;
- The piping to the ports of the outdoor unit is allowed from the side as well as from the front, bottom and rear.
Specifications
Sale Model | MDV-V120W/DRN1 | MDV-V140W/DRN1 | MDV-V160W/DRN1 | MDV-V180W/DRN1 | |||
Power supply | V-Ph-Hz | 380-415V-3N~50Hz | 380-415V-3N~50Hz | 380-415V-3N~50Hz | 380-415V-3N~50Hz | ||
Cooling | Capacity | kW | 12.3 | 14.0 | 15.5 | 17.5 | |
Input | kW | 3.25 | 3.95 | 4.52 | 5.3 | ||
EER | kW/ kW | 3.78 | 3.54 | 3.43 | 3.3 | ||
Heating | Capacity | kW | 13.2 | 15.4 | 17.0 | 19.0 | |
Input | kW | 3.47 | 4.16 | 4.77 | 5.0 | ||
COP | kW/ kW | 3.80 | 3.7 | 3.56 | 3.8 | ||
Compressor | Model | TNB306FPNMC | TNB306FPNMC | LNB42FSAMC | LNB42FSAMC | ||
Type | Rotary | Rotary | Rotary | Rotary | |||
Brand | MITSUBISHI | MITSUBISHI | MITSUBISHI | MITSUBISHI | |||
Capacity | Btu/h | 33720 | 33720 | 47700 | 47700 | ||
Input | W | 3010 | 3010 | 4240 | 4270 | ||
Rated current(RLA) | A | 9.3 | 9.3 | 12 | 12 | ||
Crankcase | W | 27 | 27 | 25 | 25 | ||
Refrigerant oil | ml | FV50S 870+630ml | FV50S 870+630ml | FV50S 1400ml | FV50S 1400ml | ||
Outdoor fan motor | Model | WZDK100-38G | WZDK100-38G | WZDK100-38G | WZDK100-38G | ||
Type | DC motor | DC motor | DC motor | DC motor | |||
Brand | Panasonic | Panasonic | Panasonic | Panasonic | |||
Insulation class | E | E | E | E | |||
Safe class | IP23 | IP23 | IP23 | IP23 | |||
Input | W | 2 x 100 | 2 x 100 | 2 x 100 | 2 x 100 | ||
Output | W | 2 x 85 | 2 x 85 | 2 x 85 | 2 x 85 | ||
Rated current | A | 2 x 0.9 | 2 x 0.9 | 2 x 0.9 | 2 x 0.9 | ||
Capacitor | uF | / | / | / | / | ||
Speed | r/min | 800 | 800 | 800 | 800 | ||
Outdoor fan | Material | ASG20 | ASG20 | ASG20 | ASG20 | ||
Type | Axial fan | Axial fan | Axial fan | Axial fan | |||
Diameter | mm | 508 | 508 | 508 | 508 | ||
Height | mm | 170 | 170 | 170 | 170 | ||
Outdoor coil | Number of rows | 2 | 2 | 2 | 2.5 | ||
Tube pitch(a)x row pitch(b) | mm | 22 x 19.05 | 22 x 19.05 | 22 x 19.05 | 22 x 19.05 | ||
Fin spacing | mm | 1.6 | 1.6 | 1.6 | 1.6 | ||
Tube outside dia.and type | mm | Ф7.94 | Ф7.94 | Ф7.94 | Ф7.94 | ||
Inner groove tube | Inner groove tube | Inner groove tube | Inner groove tube | ||||
Coil length x height | mm | 1276 x 870 | 1276 x 870 | 1276 x 870 | 1276 x 870 | ||
Number of circuits | 7 | 7 | 7 | 12 | |||
Outdoor air flow | m3/h | 6000 | 6000 | 6000 | 6800 | ||
Outdoor sound level(sound pressure level ) | dB(A) | 57 | 57 | 57 | 59 | ||
Outdoor Unit | Dimension(W x H x D) | mm | 900 x 1327 x 400 | 900 x 1327 x 400 | 900 x 1327 x 400 | 900 x 1327 x 400 | |
Packing (W x H x D) | mm | 1030 x 1456 x 435 | 1030 x 1456 x 435 | 1030 x 1456 x 435 | 1030 x 1456 x 435 | ||
Net/Gross weight | kg | 95/106 | 95/106 | 102/113 | 107/118 | ||
Refrigerant | Type | R410A | R410A | R410A | R410A | ||
Charged volume | g | 3300 | 3900 | 3900 | 4500 | ||
Throttle type | Electronic expansion valve | Electronic expansion valve | |||||
Design pressure | MPa | 4.4/2.6 | 4.4/2.6 | 4.4/2.6 | |||
Refrigerant piping | Liquid side/ Gas side | mm | Ф9.53/Ф15.9 | Ф9.53/Ф15.9 | Ф9.53/Ф19.1 | Ф9.53/Ф19.1 | |
Max. refrigerant pipe length | m | 100 | 100 | 100 | 100 | ||
Max. difference in level | m | 8 | 8 | 8 | 8 | ||
Connection wiring | Power wiring | mm2 | 5 core x2.5 | 5 core x2.5 | 5 core x2.5 | 5 core x2.5 | |
Signal wiring | mm2 | 3 core shielded wire x 0.75 | 3 core shielded wire x 0.75 | 3 core shielded wire x 0.75 | 3 core shielded wire x 0.75 | ||
Ambient temp | ℃ | (Cooling -15~43) (Heating -15~27) |
(Cooling -15~43) (Heating -15~27) |
(Cooling -15~43) (Heating -15~27) |
(Cooling -15~43) (Heating -15~27) |
||
Notes: | |||||||
1. The cooling conditions: indoor temp.: 27℃DB (80.6℉), 19℃WB (66.2℉) outdoor temp.: 35℃DB (95℉), 24℃WB (75.2℉) | |||||||
equivalent pipe length: 5m drop length: 0m. | |||||||
2. The heating conditions: indoor temp.: 20℃DB (68℉), 15℃WB (59℉) outdoor temp.: 7℃DB (44.6℉), 6℃WB (42.8℉) | |||||||
equivalent pipe length: 5m drop length: 0m. | |||||||
3. Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of *m(1.2m for | |||||||
120~180 model). During actual operation, these values are normally somewhat higher as a result of ambient conditions. | |||||||
4. The aboved datas may be changed without notice for future improvement on quality and performance. |