Operating ambient temperatures
Suggested retail price
Technology
Blue Fin
Blue fin heat exchanger cover - Protection against corrosion. Special anti-corrosion coating of the heat exchanger, protection from atmospheric phenomena and effects of aggressive environment. May differ in color (have blue, green, gold or no color at all (clear varnish)
Low Ambient Cooling
Low-temperature (season) set - used for the operation of the air conditioner in cooling mode at low ambient temperatures (usually provided in the air conditioner as an optional feature). The kit includes: the controller of the outdoor unit fan motor, compressor crankcase heater and heater drain line.
In some series of inverter split systems this option is implemented in hardware and software, thus if there is a need to use the air conditioner in the winter for cooling, you must install only drain the heater.
Multi-Bend Heat Exchanger
Increased heat. This unit uses the heat exchangers with tubes of a special design, the inner surface of which has trapezoidal notches "Innergrove cooper", which provides maximum heat transfer surface area increased. Due to this heat increases by 28%, reduced power consumption, and hence increases the efficiency of the system.
Wired remote control the chiller
Supplied with the chiller;
Provides restart with pre-set parameters, with the loss of elektenergii;
It has an informative liquid crystal display, which displays the operating modes and fault codes when they occur.
Description
At the moment, one chiller model is available - with a power of 185 kW, using R-410a refrigerant. The manufacturer does not provide for grouping.
Attention! Products are made to order! Delivery time from Midea factories is 160 days.
Specifications
Feature model | MGBL-F65W/RN1 | MGBL-D65W/RN1 | MGBL-F130W/RN1 | MGBL-F200W/RN1 | MGBL-F250W/RN1 |
---|---|---|---|---|---|
Сompressors Type(technology) | Fixed Scroll | Digital Scroll+Fixed Scroll | Fixed Scroll | Fixed Scroll | Fixed Scroll |
Power, V/Hz/Ph | 380/50/3 | 380/50/3 | 380/50/3 | 380/50/3 | 380/50/3 |
Cooling Power, kW | 65 | 65 | 130 | 185 | 250 |
Heating Power, kW | 69 | 69 | 138 | 200 | 270 |
Power Consumption, Cooling, kW | 20.4 | 20.4 | 40.8 | 63 | 78.3 |
Power Consumption, Heating, kW | 21.5 | 21.5 | 43 | 61 | 80 |
Dimensions without packing, (WxHxD), mm | 2000х1880х900 | 2000х1880х900 | 2000х2090х1685 | 2850х2110х2000 | 3800х2130х2000 |
Weight, Net/Gross, kg | 580 / 650 | 610 / 680 | 1150 / 1270 | 1730 / 2000 | 2450 / 2600 |
Noise Level, dB | 67 | 67 | 70 | 74 | 74 |
Air Flow, m3/hour | 24000 | 24000 | 48000 | 72000 | 96000 |
Nominal water flow volume, m3/hour | 11.2 | 11.2 | 22.4 | 31.8 | 43 |
Operation water/liquid temp, Celsium | 0~17 cool 22~50 heat | 0~17 cool 22~50 heat | 0~17 cool 22~50 heat | 0~17 cool 22~50 heat | 0~17 cool 22~50 heat |