Suggested retail price
Technology
Aluminium heat exchanger with hydrophilic coating
Improved wettability of the heat exchanger aluminum plates which have a special coating with a hydrophilic layer, ensuring rapid removal of condensate from the indoor unit that does not allow to quickly form of mold and bacteria, providing a more efficient operation of the air conditioner.
Central Controller
- The central controller is used for centralized management of indoor units (up to 64 indoor units can be connected via an adapter card).
- The indoor units can be divided into 20 zones, each zone can contain no more than 64 indoor units. All indoor units in one zone can only be set to the same mode. (By default, "the zone is not assigned to indoor units").
- Users can select the desired mode and temperature with a weekly schedule.
Dry Mode
Dry mode automatically selects cooling, based on the difference between fixed and temparaturoy actual room temperature. The temperature is regulated while reducing humidity repeated switching on and off of the cooling and ventilation only. when the dry mode on the remote control shows "Drop"
Multi-Bend Heat Exchanger
Increased heat. This unit uses the heat exchangers with tubes of a special design, the inner surface of which has trapezoidal notches "Innergrove cooper", which provides maximum heat transfer surface area increased. Due to this heat increases by 28%, reduced power consumption, and hence increases the efficiency of the system.
Description
The compact design of the unit with a height of only 153 mm is ideal for narrow sub-ceiling spaces, for example, for a reception room or a small meeting room, corridors.
A powerful air flow with a low noise level allows the unit to be used in rooms with high ceilings (up to 3.2m high) to maintain maximum comfort.
An integrated drain pump allows condensate to rise to a height of 750 mm.
Thanks to the presence of two folded and formaldehyde strainers in the room, high air quality is ensured.
An automatic mechanism for changing the direction of the air flow ensures its uniform distribution and maintaining a more stable temperature in the room.
A large air outlet and a wide damper help to increase the range of the angle of distribution of the conditioned air and ensure its uniform distribution over the volume of the room.
Specifications
Model | MDV-D18Q1/N1-D(B) | MDV-D22Q1/N1-D(B) | MDV-D28Q1/N1-D(B) | MDV-D36Q1/N1-D(B) | ||
Power supply | V-Hz-Ph | 220-240V-50Hz-1Ph | 220-240V-50Hz-1Ph | |||
Cooling | Capacity | kW | 1.8 | 2.2 | 2.8 | 3.6 |
Input | W | 41 | 41 | 41 | 41 | |
Rated current | A | 0.24 | 0.24 | 0.25 | 0.25 | |
Heating | Capacity | kW | 2.2 | 2.6 | 3.2 | 4.0 |
Input | W | 41 | 41 | 41 | 41 | |
Rated current | A | 0.24 | 0.24 | 0.25 | 0.25 | |
Indoor fan motor | Model | RPS12N | RPS12N | |||
Type | Single-phase AC motor | Single-phase AC motor | ||||
Brand | Welling | Welling | ||||
Input(H/M/L) | W | 29.5/26.7/25.0 | 29.5/26.7/25.0 | 31.0/27.2/25.3 | 31.0/27.2/25.3 | |
Capacitor | μF | 0.8 | 0.8 | 1.0 | 1.0 | |
Speed (H/M/L) | r/min | 1180/955/710 | 1270/1050/790 | |||
Indoor coil | Number of rows | 2 | 2 | 2 | 2 | |
Tube pitch(a) ×row pitch(b) | mm | 21×13.37 | 21×13.37 | 21×13.37 | 21×13.37 | |
Fin spacing | mm | 1.5 | 1.5 | 1.5 | 1.5 | |
Fin type | Hydrophilic aluminum | Hydrophilic aluminum | ||||
Tube outside dia. and type | mm | Ф7 Inner groove tube | Ф7 Inner groove tube | |||
Coil length × height × width | mm | 760×252.4×26.74 | 760×252.4×26.74 | |||
Number of circuits | 2 | 2 | 3 | 3 | ||
Indoor air flow (H/M/L) | m3/h | 523/404/275 | 573/456/315 | |||
Indoor noise level (H/M/L) | dB(A) | 37/34/30 | 38/34/30 | 39/37/34 | 40/38/34 | |
Indoor unit | Dimension (W×H×D) | mm | 1054×153×425 | 1054×153×425 | ||
Packing (W×H×D) | mm | 1155×245×490 | 1155×245×490 | |||
Net/Gross weight | kg | 12.5/16 | 13/16.5 | |||
Panel | Model | MBQ1-02D | ||||
Dimension (W×H×D) | mm | 1180×25×465 | 1180×25×465 | |||
Packing (W×H×D) | mm | 1232×107×517 | 1232×107×517 | |||
Net/Gross weight | kg | 3.5/5.2 | 3.5/5.2 | |||
Refrigerant type | R410A | R410A | ||||
Throttle | Type | Electronic expansion valve | Electronic expansion valve | |||
Model | D20MISZ-1R(L) | D20MISZ-1R(L) | ||||
Design pressure(H/L) | MPa | 4.4/2.6 | 4.4/2.6 | |||
Refrigerant piping | Liquid side/ Gas side | mm | Ф6.35/ Ф12.7 | Ф6.35/ Ф12.7 | ||
Connecting wiring | Power wiring | mm2 | 3×1.0 | 3×1.0 | ||
Signal wiring | mm2 | 3×0.75 | 3×0.75 | |||
Drainage water pipe diameter | mm | OD Ф25 | OD Ф25 | |||
Standard Controller | Wireless remote controller | Wireless remote controller |
Model | MDV-D45Q1/N1-D(B) | MDV-D56Q1/N1-D(B) | MDV-D71Q1/N1-D(B) | ||
Power supply | V-Hz-Ph | 220-240V-50Hz-1Ph | |||
Cooling | Capacity | kW | 4.5 | 5.6 | 7.1 |
Input | W | 48 | 48 | 60 | |
Rated current | A | 0.27 | 0.32 | 0.36 | |
Heating | Capacity | kW | 5.0 | 6.3 | 8.0 |
Input | W | 43 | 44 | 55 | |
Rated current | A | 0.27 | 0.32 | 0.36 | |
Indoor fan motor | Model | YDK38-4 | YDK43-4 | ||
Type | AC motor | AC motor | |||
Brand | Welling/ Tongde | ||||
Input | W | 39.5/33.5/25.6 | 41.5/36.0/28.0 | 56.2/40.2/28.7 | |
Capacitor | μF | 1.5 | 3.0 | 3.0 | |
Speed (h/m/l) | r/min | 930/830/710 | 1080/990/860 | 1150/1020/850 | |
Indoor coil | Number of rows | 2 | 2 | 2 | |
Tube pitch(a) × row pitch(b) | mm | 21×13.37 | 21×13.37 | 21×13.37 | |
Fin spacing | mm | 1.5 | 1.5 | 1.5 | |
Fin type | Hydrophilic aluminum | ||||
Tube outside dia. and type | mm | Ф7 Inner groove tube | |||
Coil length × height × width |
mm | 955×231×26.74 | 955×336×26.74 | ||
Number of circuits | 3 | 3 | 5 | ||
Indoor air flow (H/M/L) | m3/h | 693/600/476 | 792/688/549 | 933/749/592 | |
Indoor noise level (H/M/L) | dB(A) | 41/39/35 | 42/40/36 | 44/41/37 | |
Indoor unit | Dimension (W×H×D) | mm | 1204×189×443 | ||
Packing (W×H×D) | mm | 1370×295×505 | |||
Net/Gross weight | kg | 18.5/23.2 | 18.8/23.5 | 19.5/24.2 | |
Panel | Model | MBQ1-01D | |||
Dimension (W×H×D) | mm | 1350×25×505 | |||
Packing (W×H×D) | mm | 1410×95×560 | |||
Net/Gross weight | kg | 4/5.4 | 4/5.4 | 4/5.4 | |
Refrigerant type | R410A | ||||
Throttle | Type | Electronic expansion valve | |||
Model | D20MISZ-1R(L) | ||||
Design pressure(H/L) | MPa | 4.4/2.6 | 4.4/2.6 | 4.4/2.6 | |
Refrigerant piping | Liquid side/ Gas side | mm | Ф6.35/ Ф12.7 | Ф12.7/ Ф15.9 | Ф12.7/ Ф15.9 |
Connecting wiring | Power wiring | mm2 | 3×2.5 | 3×2.5 | 3×2.5 |
Signal wiring | mm2 | 3×0.75 | 3×0.75 | 3×0.75 | |
Drainage water pipe diameter | mm | ODФ25 | |||
Controller | Wireless remote controller | ||||
Notes: 1. Nominal cooling capacities are based on the following conditions: return air temperature: 27°CDB,19°CWB, | |||||
outdoor temperature:35°CDB,equivalent ref. Piping: 8m(horizontal) | |||||
2. Nominal heating capacities are based on the following conditions: return air temperature: 20°CDB,outdoor temperature: 7°CDB,6°CWB,equivalent ref. Piping: 8m(horizontal) | |||||
temperature: 7°CDB,6°CWB,equivalent ref. Piping: 8m(horizontal) |